P codes: Motor parameters
Code Name Data setting range Default setting
P01 No. of poles 2 to 22 4
P02 Rated capacity 0.01 to 30.00 kW (where P99 is 0, 3 or 4)
0.01 to 30.00 HP (where P99 is 1)
Rated capacity of the
motor
P03 Rated current 0.00 to 100.0 A Rated current of Fuji
standard motor
P04 Auto-tuning 0: Disable
1: Enable (Tune %R1 and %X while the motor is stopped)
2: Enable (Tune %R1 and %X while the motor is stopped and no-load
current while running)
0
P05 Online Tuning 0 : Disable
1 : Enable
0
P06 No-load current 0.00 to 50.00 A
P07 %R1 0.00 to 50.00 %
P08 %X 0.00 to 50.00 %
Rated value of Fuji
standard motor
P09 Slip compensation gain for
driving
0.0 to 200.0 %
100.0
P10 Slip compensation response
time
0.01 to 10.00 s
0.50
P11 Slip compensation gain for
braking
0.0 to 200.0 %
100.0
P12 Rated slip frequency 0.00 to 15.00 Hz Rated value of Fuji
standard motor
P99
Motor
Motor selection 0: Characteristics of motor 0 (Fuji standard motors, 8-series)
1: Characteristics of motor 1 (HP-rated motors)
3: Characteristics of motor 3 (Fuji standard motors, 6-series)
4: Other motors
0
H codes: High performance functions
Code Name Data setting range Default setting
H03 Data initialization 0: Disable initialization
1: Initialize all function code data to the factory defaults
2: Initialize motor parameters (motor 1)
3: Initialize motor parameters (motor 2)
0
H04 Times 0: Disable
1 to 10
0
H05
Auto-resetting
Reset interval 0.5 to 20.0 s 5.0
H06 Cooling fan ON/OFF control 0: Disable (Always in operation)
1: Enable (ON/OFF controllable)
0
H07 Acceleration/Deceleration pattern 0: Linear
1: S-curve (Weak)
2: S-curve (Strong)
3: Curvilinear
0
H08 Rotational Direction Limitation 0 : Disable
1 : Enable (Reverse rotation inhibited)
2 : Enable (Forward rotation inhibited)
0
H09 Select starting characteristics (Auto search) 0 : Disable
1 : Enable (At restart after momentary power failure)
2 : Enable (At restart after momentary power failure and at normal
start)
0
H11 Deceleration mode 0: Normal deceleration
1: Coast-to-stop
0
H12 Instantaneous overcurrent limiting 0: Disable
1: Enable
1
H13 Restart time 0.1 to 10.0 s Depending on the inverter
capacity
H14 Frequency fall rate 0.00: Selected deceleration time
0.01 to 100.0 Hz/s
999: Follow the current limit command
999
H16
Restart mode after
momentary power failure
Allowable momentary power
failure time
0.0 to 30.0 s
999: The longest time automatically determined by the inverter
999
H26 Mode selection 0: Disable
1: Enable (Upon detection of PTC, the inverter immediately trips
and sto