Chapter 6: Function codes and application example
30
Code Name Data setting range Default setting
H42 Capacitance of DC link bus capacitor Indication for replacing DC link bus capacitor (0000 to FFFF:
Hexadecimal)
-
H43 Cumulative run time of cooling fan Indication of cumulative run time of cooling fan for replacement -
H44 Startup Times of Motor 1 Indication of cumulative startup times -
H45 Mock Alarm 0: Disable
1: Enable (Once a mock alarm occurs, the data automatically
returns to 0)
0
H47 Initial capacitance of DC link bus capacitor Indication for replacing DC link bus capacitor (0000 to FFFF:
Hexadecimal)
Set at factory shipping
H48 Cumulative Run Time of Capacitors on the Printed Circuit
Board
Indication for replacing capacitors on the printed circuit board (0000
to FFFF: Hexadecimal). Reset able
-
H49 Starting mode
(Delay Time)
0.0 to 10.0 s
0.0
H50 Frequency 0.0: Cancel
0.1 to 400.0 Hz
0.0
H51
Non-linear V/f pattern
Voltage 0 to 240V: Output a voltage AVR-controlled (for 200V AC series)
0 to 500V: Output a voltage AVR-controlled (for 400V AC series)
0
H52 Frequency
0.0: Cancel
0.1 to 400.0 Hz
0
H53
Non-linear V/f Pattern 2
Voltage 0 to 240V: Output a voltage AVR-controlled (for 200V AC series)
0 to 500V: Output a voltage AVR-controlled (for 400V AC series)
0
H54 ACC/DEC time Jogging operation 0.00 to 3600 s 6.0
H56 Deceleration time for forced stop 0.00 to 3600 s 6.0
H61 UP/DOWN Control (Initial frequency setting)
0: 0.0
1: Last UP/DOWN cammand value on releasing run command
1
H63 Low limiter Mode selection 0: Limit by F16 (Frequency Limiter: Low) and continue to run
1: If the output frequency lowers less than the one limited by F16
(Frequency limiter: Low), decelerates to stop the motor
0
H64 Lower limiting frequency 0.0 (Depends on F16 (Frequency limiter: Low)
0.1 to 60.0 Hz
1.6
H68 Slip Compensation (Operating conditions) 0: Enable during ACC/DEC and enable at base frequency or above
1: Disable during ACC/DEC and enable at base frequency or above
2: Enable during ACC/DEC and disable at base frequency or above
3: Disable during ACC/DEC and disable at base frequency or above
0
H69 Automatic deceleration (Mode selection) 0: Disable
2: Enable (Canceled if actual deceleration time exceeds three times
the one specified by F08/E11)
4: Enable (Not canceled if actual deceleration time exceeds three
times the one specified by F08/E11)
0
H70 Overload Prevention Control 0.00: Follow deceleration time specified by F08 / E11
0.01 to 100.00 Hz/s
999: Disable
999
H71 Deceleration characteristics 0: Disable
1: Enable
0
H76 Torque Limiter (Frequency increment limit for braking) 0.0 to 400.0 Hz
5.0
H80 Output Current Fluctuation Damping Gain for Motor 1 0.00 to 0.40
0.20
H89 Reserved
H90 Reserved
H91 Reserved
H94 Cumulative run time of motor Change or reset the cumulative data -
H95 DC braking (braking response mode)
0: Slow
1: Quick
1
STOP key priority Start check function
H96 STOP key priority/start check function
0: Disable
1: Enable
2: Disable
3: Enable
Disable
Disable
Enable
Enable
0
H97 Clear alarm data 0: Does not clear alarm data
1: Clear alarm data and return to zero
0
H98 Protection/maintenance Function (Mode selection)
0 to 31: Display data on the keypad's LED monitor in decimal format
(In each bit, "0" for disabled, "1" for enabled)
Bit 0: Lower the carrier frequency automatically
Bit 1: Detect input phase loss
Bit 2: Detect output phase loss
Bit 3: Select life judgment criteria of DC link bus capacitor
Bit 4: Judge the life of DC link bus capacitor
19
(Bits 4,1,0 = 1)