A codes: Motor 2 Parameters
Code Name Data setting range Default setting
A01 Maximum Frequency 2 25 to 400.0 Hz 50.0
A02 Base Frequency 2 25 to 400.0 Hz 50.0
A03 Rated Voltage at Base Frequency 2 0: Output a voltage in proportion to input voltage
80 to 240: Output an AVR-controlled (for 200V class series)
160 to 500: Output an AVR-controlled (for 400V class series)
230
400
A04 Maximum Output Voltage 2 80 to 240V: Output an AVR-controlled (for 200V class series)
160 to 500V: Output an AVR-controlled (for400V class series)
200
400
A05 Torque Boost 2 0.0 to 20.0 %
(percentage with respect to “A03: Rated Voltage at Base Frequency
2”)
Note: This setting takes effect when A13 = 0, 1, 3 or 4.
Depending on the inverter
capacity
A06 1: general-purpose motor with shaft driven cooling fan
2: For an inverter-driven motor, non ventilated motor, or motor with
separately powered fan
1
A07 0.00 : Disable
1 to 135% of the rated current (allowable continuous drive current)
of the motor
100% of the motor rated
current
A08
Electronic Thermal Overload Protection for Motor 2
(Select motor Characteristics)
(Overload detection level)
(Thermal time constant)
0.5 to 75.0 min 5.0
A09
0.0 to 60.0 Hz
0.0
A10 0 to 100% 0
A11
DC Braking 2
(Braking starting frequency)
(Braking level)
(Braking time)
0.00 : Disable
0.01 to 30.00 s
0.00
A12 Starting Frequency 2 0.01 to 60.0 Hz 0.05
A13 Load Selection/
Auto Torque Boost/
Auto Energy Saving Operation 2
0: Variable torque load
1: Constant torque load
2: Auto torque boost
3: Auto energy saving operation (Variable torque during ACC/DEC)
4: Auto energy saving operation (Constant torque during ACC/DEC)
5: Auto energy saving operation (Auto-torque boost during
ACC/DEC)
1
A14 Control Mode Selection 2 0: V/f operation with slip compensation inactive
1: Dynamic torque vector operation
2: V/f operation with slip compensation active
3: V/f operation with optional PG interface
4: Dynamic torque vector operation with optional PG interface
0
A15 (No. of poles)
2 to 22
4
A16 (Rated capacity) 0.01 to 30.00 kW (where A39 data is 0, 3 or 4)
0.01 to 30.00 HP (where A39 data is 1)
Rated capacity of motor
A17 (Rated current)
0.00 to 100.0 A
Rated value of Fuji standard
motor
A18 (Auto Tuning)
0: Disable
1: Enable (Tune %R1 and %X while motor is stopped)
2: Enable (Tune %R1 and %X while motor is stopped and no load
current while running)
0
A19 (Online Tuning) 0: Disable
1: Enable
0
A20 (No load current) 0.00 to 50.00 A Rated value of Fuji standard
motor
A21 (%R1) 0.00 to 50.00 % Rated value of Fuji standard
motor
A22 (%X) 0.00 to 50.00 % Rated value of Fuji standard
motor
A23 (Slip compensation gain for driving) 0.0 to 200.0 % 100.0
A24 (Slip compensation response time) 0.01 to 10.00 s 0.50
A25 (Slip compensation gain for braking) 0.0 to 200.0 % 100.0
A26
Motor2
(Rated slip frequency) 0.00 to 15.0 Hz Rated value of Fuji standard
motor
A39 Motor 2 Selection 0: Motor characteristics 0 (Fuji standard motors, 8-series)
1: Motor characteristics 1 (HP rating motors)
3: Motor characteristics 3 (Fuji standard motors, 6 series)
4: Other motors
0
A40 Slip Compensation 2 (Operating conditions)
0: Enable during ACC/DEC and enable at base frequency or above
1: Disable during ACC/DEC and enable at base frequency or above
2: Enable during ACC/DEC and disable at base frequency or above
3: Disable during ACC/DEC and disable at base frequency or above
0
A41 Output Current Fluctuation
Damping Gain for Motor 2
0.00 to 0.40 0.20
A45 Cumulative Motor Run Time 2 Change or reset the cumulative data -
A46 Startup Times of Motor 2 Indication of cumulative startup times -