2. Local Mode Screen 2-45
Local Mode Screen
For a slave station
Multi-link2 (Ethernet)
For the master station
Item Description
Local Port No.
Displays the local port number of the V9 series unit. The port number of a slave station
is from “2” to “4”. Set within the total number of V9 series units.
Note that if the port number specified is the same as that already set for another V9
unit, the system will not operate correctly.
Tot al
Displays the total number of V9 units connected in multi-link2 connection. (Cannot be
changed.)
Baud Rate Displays the baud rate for between V9 series units. (Cannot be changed.)
[Multi-Link2] tab window
After changing the settings,
press the [Apply] switch to
confirm the settings.
Changes over the display of
the communication settings
between PLC1 to PLC8.
Indicates the maker,
model, and
connection port of
PLCx.
Pressing each setting field
brings up the system
keyboard to be used for
configuration.
Item Description
Local Port No.
Displays the local port number of the V9 series unit. The port number of the master
station is “1”. (Cannot be changed.)
Send Delay Time
Specify a delay time that elapses before the V9 series unit sends the next command
after receiving data from the PLC. Normally use the default setting (0).
Tot al
Displays the total number of V9 units connected in multi-link2 (Ethernet) connection.
(Cannot be changed.)
Retry Cycle
Set the cycle interval at which the master station sends an inquiry for restoration to a
slave that has encountered a problem and is disconnected.
Comm. Port No.
Set the port number for multi-link2 (Ethernet) communication.
* Set the same port number for all master and slave stations.
Target Set the IP addresses of all V9 units used as slave to respective local port numbers.
[Multi-Link2] tab window
After changing the settings,
press the [Apply] switch to
confirm the settings.
Changes over the display of
the communication settings
between PLC1 to PLC8.
Indicates the maker,
model, and
connection port of
PLCx.
Pressing each setting field
brings up the system
keyboard to be used for
configuration.