Parameter Range Description Default DSP
settings settings
roFF - rHLd roFF/rrUn/rHLd Ramp/soak command roFF dSP1-1
AH 0 - 100%FS High Alarm Setpoint 10 dSP1-2
* AL* 0 - 100%FS Low Alarm Setpoint 10 dSP1-4
Hb 0.0 - 50.0A Heater break alarm S.P. 0.0 dSP1-8
AT 0 - 2 Auto-tuning 0 dSP1-16
LoC 0 - 2 Lock-out 0 dSP1-32
Secondary Menu
P 0.0 - 999.9%FS Proportional band 5.0 dSP1-128
I 0 - 3200sec Integral time 240 dSP2-1
D 0.0 - 999.9sec Derivative time 60 dSP2-2
TC 1 - 150sec Cycle Time (output #1) dSP2-4
HYS 0 - 50%FS Hysteresis 1 dSP2-8
TC2 1 - 150sec Cycle Time (output #2) dSP2-16
CooL 0.0 - 100.0 Proportional band 1.0 dSP2-32
coefficient for cooling
db -50.0 - 50.0%FS Deadband/Overlap 0.0 dSP2-64
bAL 0 - 100% Balance 0.0/50.0 dSP2-128
Ar 0 - 100%FS Anti-reset wind-up 100%FS dSP3-1
P-n2 0 - 16 Input type code dSP3-2
P-SL -1999 - 9999 Lower range of input 0%FS dSP3-4
P-SU -1999 - 9999 Upper range of input 100%FS dSP3-8
P-dP 0 - 2 Decimal point position 0 dSP3-16
P-AH 0 - 11 Alarm Type 1 code 5 dSP3-32
* P-AL* 0 - 15 Alarm Type 2 code 9 dSP3-64
PVOF -10 - 10%FS PV offset 0 dSP3-128
SVOF -50 - 50%FS SV offset 0 dSP4-1
P-F °C/°F °C/°F selection dSP4-2
STAT -- Ramp/soak status oFF dSP4-4
SV-1 0 - 100%FS 1st S.P. 0%FS dSP4-8
TM1r 0 - 99hr 59min 1st ramping time 0.00 dSP4-16
TM1S 0 - 99hr 59min 1st soaking time 0.00 dSP4-32
SV-2 0 - 100%FS 2nd S.P. 0%FS dSP4-64
TM2r 0 - 99hr 59min 2nd ramping time 0.00 dSP4-128
TM2S 0 - 99hr 59min 2nd soaking time 0.00 dSP5-1
SV-3 0 - 100%FS 3rd S.P. 0%FS dSP5-2
TM3r 0 - 99hr 59min 3rd ramping time 0.00 dSP5-4
TM3S 0 - 99hr 59min 3rd soaking time 0.00 dSP5-8
SV-4 0 - 100%FS 4th S.P. 0%FS dSP5-16
TM4r 0 - 99hr 59min 4th ramping time 0.00 dSP5-32
TM4S 0 - 99hr 59min 4th soaking time 0.00 dSP5-64
MOD 0 -15
Ramp/soak Mode code 0 dSP5-128
PXW/PXV3 QUICK REFERENCE
Primary Menu
* Not applicable to PXV3
† Based on the model
Factory Preset Menu
Parameter Range Description Default DSP
settings settings
P-n1 0 -19 Control Action code dSP6-2
P-dF 0.0 - 900.0sec Input Filter Constant 5.0 dSP6-4
P-An 0 - 50%FS Alarm Hysteresis 1 dSP6-8
rCJ - N/A ON dSP6-16
PLC1 - N/A -3.0 dSP6-32
PHC1 - N/A 103.0 dSP6-64
PLC2 - N/A -3.0 dSP6-128
PHC2 - N/A 103.0 dSP7-1
PCUT - N/A 0 dSP7-2
FUZY OFF/ON Fuzzy control OFF dSP7-4
GAIN - N/A 1 dSP7-8
ADJ0 - Zero calibration 0 dSP7-16
ADJS - Span calibration 0 dSP7-32
OUT - N/A -3.0 dSP7-64
dSP1-7 0-255 Parameter mask -