7. Additional charge calculation
7-1. Model: AOYG18LBCB
Refrigerant type R410A
Refrigerant amount g 1,200
¢ Refrigerant charge
Total pipe length m 15 or less 20 25 (Max.)
20 g/m
Additional charge g 0 100 200
7-2. Model: AOYG24LBCB
Refrigerant type R410A
Refrigerant amount g 1,500
¢ Refrigerant charge
Total pipe length m 15 or less 20 25 30 (Max.)
20 g/m
Additional charge g 0 100 200 300
- 49 -
OUTDOOR UNIT
AOYG18-24LBCB