En-10
Wiring method6. 5.
The wiring example for Outdoor unit, indoor units and Branch box is shown in gure.
For other connections, refer to Design&Technical Manual.
Branch box (Secondary1)
Breaker1
Breaker2 Breaker2 Breaker2
Single-phase
230V 50Hz
Max.26.5A
Power supply cable
Breaker1: Earth leakage breaker
Breaker2: Circuit breaker (over current)
Breaker2
Breaker1 Breaker1 Breaker1
Outdoor unit
Single-phase
230V 50Hz
Single-phase
230V 50Hz
Single-phase
230V 50Hz
Connection cable
[Example]
Branch
box
Branch box (Secondary2)
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
(Optional
terminal)
(Optional
terminal)
(Optional
terminal)
(Primary)
Connecting of wiring6. 6.
(1) Remove the service covers and insulation sheet. And connect the wires to the
terminal in accordance with the terminal nameplate. (Fig. A, Fig. B)
(2) After connecting the wires, use binders to secure the wires. (Fig. B)
Connect the wires without applying excessive tension.•
Fig. A
Service cover
Terminal block
Fig. B
Terminal block
Binder
(Accessory)
Use the specied wire
type and connect the
wires securely.
Firmly secure the
binders so that the
wire terminals will not
receive external stress.
Please remove the excess.
Binder
Binder
(Accessory)
(3) Secure the cables using the binders under the terminal blocks, and then secure
the cables using the binders attached to the base of the valves.
Binder
(Accessory)
Binder
(4) Be sure to install the insulation sheet after the wiring is complete.
Installation method of One-touch bush
Please x the One-touch bush (accessory) as shown in the gure below.
(Pipe cover rear)
(Pipe cover front)
One-touch bush
(Accessories)
One-touch bush
(Accessories)
Front connection
Lateral connection
Rear connection