03-02
1-4. Setting the Heater Room Temperature Correction
Depending on the installed environment, the room temperature sensor may
require a correction. The settings may be selected as shown in the table below.
Setting Description Function Number Setting Value
Standard (No correction)
Warmer control (+1.0°C)
Slightly warmer control (+0.5°C)
Slightly lower control (-0.5°C)
31
00
01
02
03
Low control (-1.0°C) 04
( Factory setting)
1-5. Setting the Auto restart
Enable or disable automatic system restart after a power outage.
( Factory setting)
Setting Description
Function Number Setting Value
Yes
No
40
00
01
Auto restart is an emergency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, or external input device.
1-6. Setting the Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller temperature sensor.
( Factory setting)
Setting Description
Function Number Setting Value
No
Yes
42
00
01
If setting value is “00”,
room temperature is controlled by the indoor unit temperature sensor.
If setting value is “01”,
room temperature is controlled by either indoor unit temperature sensor or remote control unit sensor.