2) Static pressure
Select the appropriate static pressure according to the installation conditions.
Function number Setting value Setting description Factory setting
26
05 50 Pa
06 60 Pa
07 70 Pa
08 80 Pa
09 90 Pa
10 100 Pa
11 110 Pa
12 120 Pa
13 130 Pa
14 140 Pa
15 150 Pa
31 Standard (50 Pa) ♦
32 Automatic airflow adjustment
NOTE: If the static pressure is set above maximum range, the setting will be the same as the maxi-
mum.
Example:
Setting at the setting value 16 to 30 will be the same as “150 Pa” (Setting value 15).
For details, refer to "Fan performance curve" on page 13.
- 48 -
11-2. Function settings by using remote controller
11. Function settings
DUCT TYPE
ARTH30-54KMTAP