Type Inverter heat pump
Model name AOTH45KBTA AOTH54KBTA
Power supply 220―240 V ~ 50 Hz
Power supply intake Outdoor unit
Available voltage range 198—264 V
Starting current A 16.8 18.7
Fan
Airflow rate
Cooling
m
3
/h
4,450
Heating 4,450
Type × Q'ty Propeller fan × 1
Motor output W 120
Sound pressure level *
1
Cooling
dB (A)
55
Heating 57
Sound power level dB (A) 71 72
Heat exchanger type
Dimensions
(H × W × D)
mm
Main 1: 966 × 905 × 18.19
Main 2: 966 × 905 × 18.19
Sub 1: 966 × 543 × 18.19
Fin pitch
Main 1: 1.45
Main 2: 1.45
Sub 1: 1.45
Rows × Stages
Main 1: 1 × 46
Main 2: 1 × 46
Sub 1: 1 × 46
Pipe type Copper
Fin type
Type (Material) Aluminum
Surface treatment Blue fin
Compressor
Type DC twin rotary
Motor output W 2,180
Refrigerant
Type R32
Charge g 2,700
Refrigerant oil
Type RmM68AF
Amount
cm
3
800
Enclosure
Material Steel sheet
Color
Beige
Approximate color of Munsell 10YR 7.5/1.0
Dimensions
(H × W × D)
Net
mm
998 × 940 × 320
Gross 1,176 × 1,027 × 445
Weight
Net
kg
67
Gross 76
Connection pipe
Size
Liquid
mm (in)
Ø9.52 (Ø3/8)
Gas Ø15.88 (Ø5/8)
Method Flare
Pre-charge length
m
30
Max. length 50
Max. height difference 30
Operation range
Cooling
°C
-10 to 50*
2
Heating -15 to 24
Drain hose
Material LDPE
Tip diameter mm Ø13.0 (I. D.), Ø16.0 to Ø16.7 (O. D.)
International protection rating IPX4
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length: 7.5m, Height difference: 0 m.
Protective function might work when using it outside the operation range.
*
1
: Sound pressure level
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
*
2
: Suction temperature of the outdoor unit.
- 61 -
1. Specifications
OUTDOOR UNIT
AOTH30-54KBTA
OUTDOOR UNIT
AOTH30-54KBTA