When function setting is "Operation/Stop" mode 2
In the case of "Edge" input
Function
setting /
Rotary SW of
External input and
output PCB
External input Input signal Command
46-03
- Input of indoor unit Terminal
Off → On Operation
On → Off
Stop (R.C.
disabled)
60-00 / 1
External input and
output PCB
Input 1
Off → On Operation
On → Off
Stop (R.C.
disabled)
On
Input
Off
Operation
Indoor unit
Stop
(R.C. disabled)
Remote controller
On OnOff
In the case of "Pulse" input
Function
setting /
Rotary SW of
External input and
output PCB
External input Input signal Command
46-03 60-00 / 1
External input and
output PCB
Input 1 Pulse Operation
Input 2 Pulse
Stop (R.C.
disabled)
On
On
Off
Operation
Stop
Remote controller
On
Off
Indoor unit
Input 1
Input 2
(R.C. disabled)
Off
On
NOTES:
When "Operation/Stop" mode 2 function is used with forming a remote controller group,
connect the same equipment to each indoor unit within the group.
DESIGN & TECHNICAL MANUAL
- 28 -