10. Electrical characteristics
Model name AOHG72LRLA AOHG90LRLA
Power supply
Voltage V 3N 400 ~
Frequency Hz 50
Max operating current A 13.3 14.6
Wiring spec. *1
Circuit breaker current A 30
Power cable
mm
2
6.0
Connection cable *2
mm
2
1.5
Limited wiring
length
m 101
*1: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
As the regulations of wire size and circuit breaker differ in each country or region, select appropri-
ate devices complied to the regional standard.
*2: Limit voltage drop to less than 2%. Increase conductor size if voltage drop is 2% or more.
- 67 -