12-2. Function settings by using remote controller
Some function settings can be changed on the remote controller. After confirming the setting pro-
cedure and the content of each function setting, select appropriate functions for your installation
environment.
NOTE:
Incorrect settings can cause a product malfunction.
¢
Remote controller address setting
Remote controller address confirmation
NOTE:
The address of this remote controller is set automatically. Do not change the indoor unit
remote controller address from the factory setting "0". (Verify that the address is "0".)
1. To activate the address setting mode, hold down the three buttons of “MENU”, “<“, and “EN-
TER” at the same time for 2 seconds or longer. Menu 2 setting screen is displayed.
2. Select the “15” in Menu 2 settings. Then press the “ENTER” button.
3. The address of this unit is displayed on the screen.
” is displayed:
Address automatically
Remote controller address
allocated
Not displayed:
Address manually
allocated
01 to 32
Press the “ENTER” button to return to the Menu 2 item selection screen.