EasyManua.ls Logo

Fujitsu GENERAL ARHG72LHTA - Model: AOHG90 LRLA

Fujitsu GENERAL ARHG72LHTA
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-2. Model: AOHG90LRLA
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 20 30 40 50 60 70 80 90 100
Height difference H (m)
Indoor
unit is
higher
than
outdoor
unit *1
30 0.898 0.874 0.850 0.826 0.803 0.780 0.756 0.732
20 0.938 0.913 0.889 0.864 0.840 0.817 0.793 0.769 0.744
10 0.978 0.953 0.928 0.903 0.879 0.854 0.830 0.806 0.781 0.757
7.5 0.988 0.982 0.957 0.932 0.907 0.882 0.858 0.834 0.809 0.784 0.760
5 0.992 0.992 0.986 0.961 0.935 0.911 0.886 0.861 0.837 0.812 0.788 0.763
0 1.000 1.000 0.994 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
Indoor
unit is
lower
than
outdoor
unit *2
-5 1.000 1.000 0.994 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
-7.5 1.000 0.994 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
-10 0.994 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
-20 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
-30 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
HEATING
Pipe length (m)
5 7.5 10 20 30 40 50 60 70 80 90 100
Height difference H (m)
Indoor
unit is
higher
than
outdoor
unit *1
30 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
20 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
10 0.997 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
7.5 1.000 0.997 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
5 1.000 1.000 0.997 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
0 1.000 1.000 0.997 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
Indoor
unit is
lower
than
outdoor
unit *2
-5 0.995 0.995 0.992 0.982 0.972 0.961 0.951 0.941 0.933 0.923 0.913 0.903
-7.5 0.993 0.990 0.980 0.970 0.959 0.949 0.939 0.931 0.921 0.911 0.901
-10 0.987 0.977 0.967 0.956 0.946 0.937 0.928 0.918 0.908 0.898
-20 0.967 0.957 0.947 0.937 0.927 0.919 0.909 0.899 0.889
-30 0.948 0.937 0.927 0.918 0.909 0.900 0.890 0.880
DESIGN & TECHNICAL MANUAL
- 62 -
OUTDOOR UNIT
AOHG72-90LRLA

Table of Contents