7. Additional charge calculation
7-1. Model: AOHG72LRLA
Refrigerant type R410A
Factory charge amount g 5,600
¢ Refrigerant charge
Total pipe length m
30 or
less
40 50 60 70 80 90
100
(Max.)
110 g/m
Additional
charge amount
g 0 1,100 2,200 3,300 4,400 5,500 6,600 7,700
7-2. Model: AOHG90LRLA
Refrigerant type R410A
Factory charge amount g 7,100
¢ Refrigerant charge
Total pipe length m
30 or
less
40 50 60 70 80 90
100
(Max.)
110 g/m
Additional
charge amount
g 0 1,100 2,200 3,300 4,400 5,500 6,600 7,700
- 63 -