6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit *
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
HH
6-1. Model: AOHG72LRLA
NOTE:
Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 20 30 40 50 60 70 80 90 100
Height difference H (m)
Indoor
unit is
higher
than
outdoor
unit *1
30 0.898 0.874 0.850 0.826 0.803 0.780 0.756 0.732
20 0.938 0.913 0.889 0.864 0.840 0.817 0.793 0.769 0.744
10 0.978 0.953 0.928 0.903 0.879 0.854 0.830 0.806 0.781 0.757
7.5 0.988 0.982 0.957 0.932 0.907 0.882 0.858 0.834 0.809 0.784 0.760
5 0.992 0.992 0.986 0.961 0.935 0.911 0.886 0.861 0.837 0.812 0.788 0.763
0 1.000 1.000 0.994 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
Indoor
unit is
lower
than
outdoor
unit *2
-5 1.000 1.000 0.994 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
-7.5 1.000 0.994 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
-10 0.994 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
-20 0.969 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
-30 0.943 0.918 0.893 0.868 0.844 0.819 0.794 0.769
HEATING
Pipe length (m)
5 7.5 10 20 30 40 50 60 70 80 90 100
Height difference H (m)
Indoor
unit is
higher
than
outdoor
unit *1
30 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
20 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
10 0.997 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
7.5 1.000 0.997 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
5 1.000 1.000 0.997 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
0 1.000 1.000 0.997 0.987 0.977 0.966 0.956 0.946 0.938 0.928 0.918 0.908
Indoor
unit is
lower
than
outdoor
unit *2
-5 0.995 0.995 0.992 0.982 0.972 0.961 0.951 0.941 0.933 0.923 0.913 0.903
-7.5 0.993 0.990 0.980 0.970 0.959 0.949 0.939 0.931 0.921 0.911 0.901
-10 0.987 0.977 0.967 0.956 0.946 0.937 0.928 0.918 0.908 0.898
-20 0.967 0.957 0.947 0.937 0.927 0.919 0.909 0.899 0.889
-30 0.948 0.937 0.927 0.918 0.909 0.900 0.890 0.880
- 61 -
OUTDOOR UNIT
AOHG72-90LRLA