12-2. External output
With using external output function, some status signals are transmitted to the control PCB, and
the related LED lamp indicates the status of this product.
¢
Error status output
Signal on air conditioner error status is generated when a malfunction occurs.
Circuit diagram example (CN136)
Signal
Outdoor unit
control PCB
Connected unit
Connector
1
2
Locally purchased
*10 m
Vcc
+
+
-
Load
Vcc
Power
supply
CN136
• 1: Power supply
Voltage (Vcc): DC 24 V or less
• 2: Load
DC 500 mA or less
• *: Make the distance from the PCB to the
connected unit within 10 m.
Error
Normal
On
Off
Error status
Output signal
Optional part
Part name Model name Exterior
External connect kit UTY-XWZXZ3
- 71 -
OUTDOOR UNIT
AOHG72-90LRLA