2) Static pressure
Select the appropriate static pressure according to the installation conditions.
Function number Setting value Setting description Factory setting
26
05 50 Pa
06 60 Pa
07 70 Pa
08 80 Pa
09 90 Pa
10 100 Pa
11 110 Pa
12 120 Pa
13 130 Pa
14 140 Pa
15 150 Pa
16 160 Pa
17 170 Pa
18 180 Pa
19 190 Pa
20 200 Pa
31 Standard (72 Pa)
32 Automatic airflow adjustment
NOTE:
Range of static pressure is different by model.
Type name Setting of static pressure range
72 type 50 to 150 Pa
90 type 50 to 200 Pa
3) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature correction values show the difference from the Standard setting "00" (manufac-
turer’s recommended value).
Function number Setting value Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00 Standard setting
01 No correction 0.0 °C
02 -0.5 °C
More cooling
Less heating
03 -1.0 °C
04 -1.5 °C
05 -2.0 °C
06 -2.5 °C
07 -3.0 °C
08 -3.5 °C
09 -4.0 °C
10 +0.5 °C
Less cooling
More heating
11 +1.0 °C
12 +1.5 °C
13 +2.0 °C
14 +2.5 °C
15 +3.0 °C
16 +3.5 °C
17 +4.0 °C