LED lamp Function or operation method
(1) POWER/MODE Green
Lights on while power on.
Local setting in outdoor unit or error code is displayed with blink.
(2) ERROR Red Blinks during error operation.
(3) PUMP DOWN (L1) Orange Lights on during pump down operation.
(4)
LOW NOISE MODE
(L2 and L3)
Orange
Lights on during “Low noise mode” when local setting is activated.
(Lighting pattern of L2 and L3 indicates low noise level.)
(5)
PEAK CUT MODE
(L4, L5, and L6)
Orange
Lights on during “Peak cut mode” when local setting is activated.
(Lighting pattern of L4, L5, and L6 indicates peak cut level.)
Switch button Function or operation method
SW107 MODE Switches between “Local setting” and “Error code display”.
SW108 SELECT Switches between the individual “Local settings” and the “Error code displays”.
SW109 ENTER Switches between the individual “Local settings” and the “Error code displays”.
SW112 EXIT Returns to “Operation status display”.
SW110 PUMP DOWN Starts the pump down operation.
¢
Function setting table
No. Setting item
LED display
Factory
setting
POWER
MODE
ERROR
PUMP
DOWN
LOW NOISE PEAK CUT
(L1) (L2) (L3) (L4) (L5) (L6)
1
Low noise
mode setting
Level 1
Blink
(9 times)
Level 2
2
Peak cut
mode setting
Level 1
Level 2
Level 3
Level 4
Sign "○": Lights off, "●": Lights on
No. Setting item Content
1 Low noise mode setting
By using the "Low noise mode", the limit of the noise level will be set to
decrease the noise level. The mode comes in 2 levels which can be set
accordingly.
To turn on the mode, use the external input terminal (CN131).
By using this mode, the cooling/heating performance may decrease.
Depending on the operating condition, the noise level may not decrease even
if the Low noise mode is on.
2 Peak cut mode setting
The capacity limit can be selected when operating with the “Peak Cut mode.”
The operation selection can be done by external input terminal (CN132).
The lower the level, the more the effect of energy saving, but the cooling/
heating performance decreases.
Noise level as low noise mode setting
Unit: dB (A)
AOHG72LRLA AOHG90LRLA
Cooling Heating Cooling Heating
Level1 53 53 53 55
Level2 51 51 51 53
DESIGN & TECHNICAL MANUAL
- 74 -
OUTDOOR UNIT
AOHG72-90LRLA