Fujitsu UTY-RNRUZ5
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
(3) Select the category about which you want to monitor.
(4) If you select [Sensor ID], input the ID of the monitoring
item on the next screen.
(3) (4)
Back
Advanced Selection
Outdoor Unit
Sensor IDOperating Time
Indoor Unit
0
CL
5
1
6
2
7
3
8
4
9
00
-
001
1
Cancel OK
Sensor ID
Information on the selected
category is displayed. When
the screen has multiple pages,
they can be switched by
touching the [Next Page] or
[Previous Page].
Return Air Temp.
[18.0
]
[18.0
]
Room Temp.
[18.0
]
Heat ex. inlet temp.
[18.0
]
Heat ex. middle temp.
[18.0
]
Heat ex. outlet temp.
[18.0
]
Discharge temp.
Page 1/ 3
Indoor Unit
Item [Value]
End
Next
Page
When the [End] is touched, the display returns to the
Advanced Selection” screen.
4 OPERATION TIPS
4-1 Selectable Modes (for VRF system)
There are restrictions on the selectable modes depending on
thesystemcongurationandoperationstatus.
4-1-1 Heatrecoverysystem
(a) When single indoor unit connected to RB unit
All the modes can be selected.
(b) When a master indoor unit is set in an RB group, only
the mode selected at the master indoor unit (*1) can be
used.(*1:“Fan”cannotbeselectedattheindoorunit
including the master indoor unit.)
(c) When a master indoor unit is not set in the RB Group,
refer to the following table.
Status Selectable Not selectable
Other indoor unit is in cool-
ing operation.
Cool, Dry Custom Auto,
Heat, Fan
Other indoor unit is in dehu-
midifying operation.
Cool, Dry Custom Auto,
Heat, Fan
Other indoor unit is in heat-
ing operation.
Heat Custom Auto,
Cool, Dry, Fan
Other indoor unit is in anti
freeze operation.
Heat Custom Auto,
Cool, Dry, Fan
4-1-2 Whenindoorunitsareconnectedforcooling
onlyinheatrecoverysystem
(a) Refertothefollowingtable:
Status Selectable Not selectable
At any time
Custom auto,
Cool, Dry, Fan
Heat
4-1-3 RBpriorityconnectioninheatrecoverysystem
(a) For indoor units or RB groups by RB priority connec-
tion,refertothefollowingtable:
Status Selectable Not selectable
Cooling priority is set by
external input.
Cool, Dry Custom Auto,
Heat, Fan
Heating priority is set by
external input.
Heat Custom Auto,
Cool, Dry, Fan
4-1-4 Heatpumpsystem
(a) Refertothefollowingtable:
Status Selectable Not selectable
Other indoor unit is in cool-
ing operation.
Cool, Dry Custom Auto,
Heat, Fan
Other indoor unit is in dehu-
midifying operation.
Cool, Dry Custom Auto,
Heat, Fan
Other indoor unit is in heat-
ing operation.
Heat Custom Auto,
Cool, Dry, Fan
Other indoor unit is in anti
freeze operation.
Heat Custom Auto,
Cool, Dry, Fan
(b) When a master indoor unit is set in a refrigerant system,
only the mode selected at the master indoor unit (*2)
canbeused.(*2:“Fan”cannotbeselectedattheindoor
unit including the master indoor unit.)
4-1-5 Outdoorunitpriorityconnectioninheatpump
system
(a) Refertothefollowingtable:
Status Selectable Not selectable
Cooling priority is set by
external input.
Cool, Dry Custom Auto,
Heat, Fan
Heating priority is set by
external input.
Heat Custom Auto,
Cool, Dry, Fan
4-2 Vericationscreenwhensettingis
complete
Thevericationscreenwhichis
displayed when a setting is com-
plete is displayed for approximately
3 seconds. When this screen is
touched, the display switches to
the next screen.
(Example of screen)
Auto Off Timer
Setting changed.
4-3 Settabletemperaturerange
The settable temperature range by operation mode and
indoor unit setting is shown in the table below.
Cool/Dry 64 to 88 °F (18 to 30 °C)
Heat
VRFsystem:48to88°F(10to30°C)
Othersystem:60to88°F(16to30°C)
Custom Auto
Same as the above range, but there are
temperatures that cannot be set due to the
deadband.
En-25