- (OU01 - 12) -
Outdoor unit / 3 phase
OUTDOOR UNIT
WO
K112-160LC
OUTDOOR UNIT
WO
K112-160LC
EXTERNAL INPUT & OUTPUT5-2.
MODELS : WO
K112L, WO
K140L, WO
K160L
Input Output Connector Remarks
Low noise mode ― CN19
See external
input/output settings
for details.
Peak cut mode ― CN19
― Compressor status CN18
EXTERNAL INPUT
ON/OFF of the "Low noise mode" and "Peak cut mode" functions can be specied by external
signal.
Low noise mode
z
On-site work like the following also reduces the operating sound of the outdoor unit from the •
normal sound.
The air conditioner is set to the "Low noise mode" by applying the contact input of a commercial
timer or ON/OFF switch to a connector on the outdoor control PC board.
* Performance may drop depending on the outside air temperature condition, etc.
Circuit diagram example
Outdoor
control PC board
Connected unit
Connector
1
2
3
Signal
Field supply
* Make the distance from the PC board to the connected unit within 10 m.
Surely insulate with
insulation tape etc. since
this wire is not used.
*10 m
Red
White
Black
Vcc
R
SW
Vcc
Power
supply
Use the following parts and construct a circuit like that shown above. •
Input signal∙∙∙ON : Low noise mode / OFF : Normal operation •
* Set the "Low noise mode" type by "Push switch" on the outdoor control PC board.
ON
OFF
ON
OFF
Input signal
Low noise mode
Parts (Optional)
Model name
UTY-XWZ X Z2
Wire (External input)) : Red / White / Black
1) Power supply
●Voltage (Chart sign=Vcc) : DC 5V to 24V
●The current capacity : About 100mA
2) Switch (Chart sign=SW)
● Toggle switch or Rocker switch, etc : Switch which maintains the
states.
● Prepare switches which are enough capable for DC 10mA
current or more
3) Resistance (Chart sign=R)
●Adjust the resistance for current to about DC 10mA
(Example)
●In case of Vcc=DC 5V : Rated resistance value 470Ω 1/4W
●In case of Vcc=DC 12V : Rated resistance value 1kΩ 1/4W
●In case of Vcc=DC 24V : Rated resistance value 2.2kΩ 1/4W