SAFETY DEVICES9.
Protection from
Model
WO
Û
K112LCT WO
Û
K140LCT WO
Û
K160LCT
Circuit protection Current fuse (Main PCB)
5A 250V
3.15A 250V
10A 250V
Fan motor protection Thermal protecter
OFF: 150±20ºC
ON: 120±20ºC
Compressor protection
Thermal protection program
(Compressor temp.)
OFF: 112ºC
ON: 80ºC
Thermal protection program
(Discharge temp.)
OFF: 115ºC
ON: After 7 minutes
High pressure protection
Thermal protection program
(Heat exchanger temp.)
OFF: 68ºC
ON: 6C
Pressure sensor
OFF: 4.2MPa
ON: 3.0MPa
Low pressure protection
(Cooling mode only)
Pressure sensor
OFF: 0.12MPa
ON: 0.15MPa