- (CS01 - 32) -
Control system
- (CS01 - 32) -
CONTROL
SYSTEM
CONTROL
SYSTEM
Cooling Characteristic
LINE FUNCTION
908 Flow temp setpoint at OT 25°C
909 Flow temp setpoint at OT 35°C
The controller computes the ow temperature
required for a given composite outdoor temperature
based on the cooling characteristic. This is dened
by two reference points (ow setpoint at 25°C and
at 35°C).
Flow temp setpoint at OT 25°C
This is the cooling ow temperature required when
the composite outdoor temperature is 25°C, without
summer compensation.
Flow temp setpoint at OT 35°C
This is the cooling ow temperature required when
the composite outdoor temperature is 35°C, without
summer compensation.
25°C 35°C
909
908
Flow temp
setpoint
Composite
OT
The cooling characteristic is adjusted for a 25°C
room temperature setpoint. If the room temperature
setpoint is changed the curve will automatically
adapt.
Eco
LINE FUNCTION
912 Cooling limit at OT
913 Lock time at end of heating