EasyManua.ls Logo

Fujitsu WOxK112LCT - 2. SPECIFICATIONS

Fujitsu WOxK112LCT
139 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- (HU01 - 03) -
Hydraulic unit / 3 phase
HYDRAULIC UNIT
WS
K160DC9
HYDRAULIC UNIT
WS
K160DC9
SPECIFICATIONS2.
TECHNICAL SPECIFICATIONS2-1.
Model name (Hydraulic unit) WS
Û
K160DC9
Model name (Outdoor unit) WO
Û
K112LCT WO
Û
K140LCT WO
Û
K160LCT
Input power
Enclosure
Heating
Rated
kW
0.08
Max. *1 9
Casing
Colour WHITE
Material 8/10mm DC01 + EZ (5µ)
Dimensions
(H x W x D)
Net
mm
800 x 450 x 457
Gross 955 x 550 x 530
Weight
Net
kg
42
Gross 48
Main components
Pump
Type Water cooled
Speed setting Variable pressure / Constant pressure
Input power W 70 *2
Water side
Heat
exchanger
Type Double-tube
Q’ty 1
Water volume l 16
Water ow
rate Min.
l/h 1200 1500 1700
Water ow
rate Nom.
Heating
l/h
1891 2357 2639
Cooling 1902
Insulation material polyurethane
Expansion
vessel
Volume l 8
Max. water
pressure
bar
4.5
Pre pressure 1 bar (+/-20%)
Water circuit
Piping connections diameter
mm
ø25.4(ø1 in.)
Piping ø25.4(ø1 in.)
Safety valve bar 3
Manometer Yes
Drain valve / Fill valve Yes
Air purge valve Yes
Connection pipe
(Refrigerant circuit)
Liquid side diameter
mm
ø9.52(ø3/8 in.)
Gas side diameter ø15.88(ø5/8 in.)
Method Flare
Sound pressure level Heating dBA 39
Operation range Waterside Heating °C 8 to 60
Pump rank A
*1: With electric back-up heater.
*2: The value is at Full speed and full ow.

Table of Contents