- (HU01 - 03) -
Hydraulic unit / 3 phase
HYDRAULIC UNIT
WS
K160DC9
HYDRAULIC UNIT
WS
K160DC9
SPECIFICATIONS2.
TECHNICAL SPECIFICATIONS2-1.
Model name (Hydraulic unit) WS
Û
K160DC9
Model name (Outdoor unit) WO
Û
K112LCT WO
Û
K140LCT WO
Û
K160LCT
Input power
Enclosure
Heating
Rated
kW
0.08
Max. *1 9
Casing
Colour WHITE
Material 8/10mm DC01 + EZ (5µ)
Dimensions
(H x W x D)
Net
mm
800 x 450 x 457
Gross 955 x 550 x 530
Weight
Net
kg
42
Gross 48
Main components
Pump
Type Water cooled
Speed setting Variable pressure / Constant pressure
Input power W 70 *2
Water side
Heat
exchanger
Type Double-tube
Q’ty 1
Water volume l 16
Water ow
rate Min.
l/h 1200 1500 1700
Water ow
rate Nom.
Heating
l/h
1891 2357 2639
Cooling 1902
Insulation material polyurethane
Expansion
vessel
Volume l 8
Max. water
pressure
bar
4.5
Pre pressure 1 bar (+/-20%)
Water circuit
Piping connections diameter
mm
ø25.4(ø1 in.)
Piping ø25.4(ø1 in.)
Safety valve bar 3
Manometer Yes
Drain valve / Fill valve Yes
Air purge valve Yes
Connection pipe
(Refrigerant circuit)
Liquid side diameter
mm
ø9.52(ø3/8 in.)
Gas side diameter ø15.88(ø5/8 in.)
Method Flare
Sound pressure level Heating dBA 39
Operation range Waterside Heating °C 8 to 60
Pump rank A
*1: With electric back-up heater.
*2: The value is at Full speed and full ow.