EasyManua.ls Logo

Fujitsu WOxK112LCT - Page 67

Fujitsu WOxK112LCT
139 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- (CS01 - 22) -
Control system
- (CS01 - 22) -
CONTROL
SYSTEM
CONTROL
SYSTEM
Time program functions (Heating circuit 1 & 2, DHW, Cooling)
z
Several control programs are available for the
heating circuits and the production of DHW. They
are initiated in "Automatic" mode and control the
change in temperature levels (and therefore the
associated setpoints, reduced and comfort) via the
adjusted changeover times.
Enter changeover times:
Changeover times can be adjusted in a combined
way, i.e., identical times for several days or distinct
times for certain days. Preselecting groups of days
(e.g., Mon...Fri and Sat...Sun) having the same
changeover times make adjustment of the
changeover program considerably shorter.
Changeover Points
LINE FUNCTION
HC1 HC2 4/DHW 5
500 520 560 600 Preselection
(Mo-Su / Mo-Fr / Sa – Su / Mo...Su)
501 521 561 601 1
st
phase on
502 522 562 602 1
st
phase off
503 523 563 603 2
nd
phase on
504 524 564 604 2
nd
phase off
505 525 565 605 3
rd
phase on
506 526 566 606 3
rd
phase off
Standard Program
LINE FUNCTION
516, 536, 576, 616 Default values
(No /Yes)
All time programs can be reset to factory settings.
Each time program has its own programming line
for this reset action.
In this case, individual settings will be lost!
Holidays
LINE FUNCTION
HC1 HC2
641 651 Preselection
642 652 Period start (Day / Month)
643 653 Period end (Day / Month)
648 658 Operation level
The holiday program enables changing the heating
circuits over to a selected operating level according
to the date (calendar).
Important:
The holiday program can be used only in the
automatic mode.

Table of Contents