INSTALLATION AND
OPERATION MANUAL
Caliber
High E ciency Hydronic Boilers
300,000 - 850,000 BTU/HR
Serial/ National
Board Number
Model
Fulton Order
Sold To
Job Name
Date
CAL-IOM-2012-1220

Table of Contents

Questions and Answers

  • M
    Meredith ChapmanAug 15, 2025
    What to do if Gas Pressure alarm is annunciated on FULTON Boiler?
    • K
      Kelli WrightAug 15, 2025
      If the Gas Pressure alarm is annunciated on your FULTON Boiler, it means that either the gas pressure is insufficient or the gas pressure to the manifold is too high for the boiler's safe operation, causing the burner to shut down. You should locate the cause and correct it. If there's a high gas manifold pressure condition, it's crucial to have qualified service personnel fix the problem before you restart the boiler.
  • R
    Robert MorrisAug 18, 2025
    What to do if High water temp alarm is annunciated on FULTON Boiler?
    • J
      Jill VaughanAug 18, 2025
      If the high water temperature alarm is annunciated on your FULTON Boiler, the boiler water has exceeded both the operating and high-limit temperature. You need to locate the cause and correct it. After resetting the SOLA control, the system should return to normal operation, assuming all other limits are within acceptable ranges.
  • N
    nelsonarielAug 22, 2025
    How to troubleshoot Low Air Flow Supply on FULTON Boiler?
    • J
      Justin BowenAug 22, 2025
      Low Air is annunciated on your FULTON Boiler if the airflow switch detects low airflow through the boiler. The air switch is factory set and shouldn't be adjusted in the field. A persistent low air indication doesn't necessarily mean the low air switch is faulty. Check that the blower is powered and the feedback plugs are connected to the blower. Also, check that the burner is clean by observing through the venturi. Ensure the blower purge speed and low fire speed are correctly displayed on the touch screen. Finally, inspect the vent and air inlet for any obstructions.
  • P
    Peter ScottAug 25, 2025
    What happens if there is a power outage to FULTON Boiler room?
    • C
      Charles AllenAug 26, 2025
      If there is a power outage to the FULTON Boiler system, the entire boiler system will be disabled and de-energized. When power is restored, the boiler will restart automatically unless it was in a lockout position when the outage occurred.
  • A
    Ashley GordonAug 28, 2025
    Why does High Back Pressure Switch trip FULTON Boiler?
    • J
      James GonzalezAug 28, 2025
      A High Back Pressure Switch trip or boiler shutdown on your FULTON Boiler is caused by excessive vent pressure. This condition will automatically recycle, so the boiler will attempt to relight. You should check the vent and heat exchanger for any obstructions and clean them.
  • J
    johnmaloneAug 31, 2025
    What to do if the main flame fails during firing period on FULTON Boiler?
    • K
      katherine89Sep 1, 2025
      If the main flame fails during the firing period in your FULTON Boiler, the main gas control valve is de-energized, and the control enters 'lockout' mode. This flame failure will illuminate an indicator. The programmer must be manually reset.
  • B
    Betty BrewerSep 3, 2025
    What to do if Manual Reset limit device trips on FULTON Boiler?
    • N
      Nicole PotterSep 3, 2025
      Manual Reset Limits on your FULTON Boiler include the flame safeguard, high or low gas pressure, and high-temperature limit. Do not reset without determining and correcting the cause.
  • T
    taraallenSep 7, 2025
    What causes Ignition Failure on FULTON Boiler?
    • D
      Darlene StewartSep 7, 2025
      If the UV scanner doesn't detect the flame during the 4-second trial-for-ignition period on your FULTON Boiler, the gas valve and spark ignition are de-energized, and a safety lockout occurs. Identify and correct the issue, then reset via the SOLA Control.
  • M
    Michael MorrisSep 12, 2025
    What causes lock out due to insufficient flow of heat transfer medium in FULTON Boiler?
    • D
      Deborah CordovaSep 12, 2025
      The FULTON Boiler requires a minimum flow of heat transfer medium. When the required flow is resumed, the boiler will resume operation. Identify and correct the cause of the insufficient flow.

Summary

Introduction

Warnings & Cautions

Explains warnings and cautions for safety and equipment protection.

Installation

Install Water Piping

Details on connecting water lines, flow rates, and system requirements.

Meet Water Chemistry Requirements

Outlines required water quality and treatment for the boiler.

Fill the Boiler With Water

Step-by-step instructions for filling the boiler with water.

Install Gas Piping

Guidelines for installing natural gas piping according to codes.

Electrical Connections

Instructions for making electrical connections to the boiler.

Operation

Perform Pre-Start-Up Inspection

Checklist for pre-start-up checks to ensure safe operation.

SETTING COMBUSTION

Procedure for setting the boiler's combustion parameters using a analyzer.

Maintenance

Warranty & Parts

Standard Warranty for Fulton Caliber Hydronic Boilers

Details on thermal shock, pressure vessel/heat exchanger warranties.

FULTON Caliber Specifications

General IconGeneral
BrandFULTON
ModelCaliber
CategoryBoiler
LanguageEnglish

Related product manuals