2 INSTALLATION
© Fulton 2018
2-14
VSRT_IOM_2018-1213
FRONT VIEW
RIGHT SIDE VIEW
TOP VIEW
DRAWN BY:
CHECKED BY:
B.O.M. REVIEW: APPROVED BY:
ELECTRICAL REVIEW:
MECHANICAL REVIEW:
REVISIONDRAWING NUMBER
JOB NUMBER:
PROJECT NAME:
PROJECT MANAGER:
DESCRIPTION:
VSRT-60 GAS FIRED MODULATED STEAM BOILER
(150 PSI)
9-SR-060312 - PDS
-
T. KENNEDY
2/14/2018
N/A
N/A
W.W.
2/16/2018
N/A
E.B.W.
2/16/2018
This design and drawings are
proprietary and are the
exclusive property of The
Fulton Companies. The
corporation do
es not permit
their use except with prior
written consent.
The items shown in this
drawing may be covered by
one or more patents of The
Fulton Companies.
SHEET 1 OF 1
THIRD ANGLE PROJECTION
TOLERANCES
FRACTION &
WHOLE VALUE
(1) PLACE DEC.
(2) PLACE DEC.
1/8
UNLESS OTHERWISE NOTED
DIMENSIONS ARE IN INCHES
0.03
(3) PLACE DEC.
SURFACE FINISH
250 MICRO-INCHES
0.005
0.5 DEGANGLE
0.015
Fulton Steam Solutions, Inc.
F
u
l
o
t
n
SEE NOTES 3 AND 10
SEE
NOTE
4
CUSTOMER CONNECTIONS
ITEM DESCRIPTION SIZE TYPE
A FEED WATER INLET 1" N.P.T.
B BLOWDOWN OUTLET
1 1/2"
N.P.T.
C STEAM OUTLET
4"
150#
D EXHAUST STACK
10"
- - -
E
SAFETY RELIEF VALVE*
1 1/4"
N.P.T.
F
FUEL INLET
1 1/2"
N.P.T.
G WATER COLUMN DRAIN 1" N.P.T.
H SIGHT GLASS DRAIN
1/4"
N.P.T.
J WATER SAMPLE PORT
1/4"
N.P.T.
K STEAM SAMPLE PORT
1/4"
N.P.T.
L SURFACE BLOWDOWN
3/4"
N.P.T.
M
HIGH WATER PROTECTION (CAPPED)
3/4"
N.P.T.
N SINGLE SOURCE POWER
- - -
N.P.T.
P COMBUSTION AIR INLET
6"
- - -
R
AUXILIARY WATER COLUMN (CAPPED)
1"
N.P.T.
S
SECONDARY SAFETY RELIEF VALVE (CAPPED) 1 1/4"
N.P.T.
S
E
E
N
O
T
E
S
4
A
N
D
1
0
H
.H
.)
28 3/16
9
84 1/4
67 3/8
49 (MIN WIDTH)
C
E
-
INITIAL RELEASE
- - - - -
REVISION HISTORY
REV REVISION DESCRIPTION B.O.M. ELEC. ENG. MECH. ENG CHECKED APPROVED
F
P
S M
21 3/8
64 5/8
99 3/16
103 1/2
NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
STEAM O
UTPUT LB/HR: FROM 0 PSIG AT 212°F (0 KG/CM² AT
100°C)
ALL CLEA
RANCES ARE FACTORY RECOMMENDATIONS. CONSULT
LOCAL J
URISDICTION FOR EXACT CODE COMPLIANCE.
FULTON
RECOMMENDS MINIMUM CLEARANCE OF 36" IN FRONT
OF ELEC
FULTON
RECOMMENDS 36" CLEARANCE BETWEEN INSPECTION
OPENING
S OF ALL BOILERS, 18" CLEARANCE OF HANDHOLES,
AND 14"
PLEASE
REFER TO THE O&M MANUAL FOR ADDITIONAL
INFORM
ATION REGARDING CLEARANCES AND INSTALLATION
INSTRUC
ALL DIM
ENSIONS INSIDE ( ) DENOTE REFERENCE DIMENSIONS.
ALL DIM
ENSIONS INSIDE
DENOTE OVERALL DIMENSIONS.
WE RESE
RVE THE RIGHT TO CHANGE SPECIFICATIONS
AND/OR
DIMENSIONS. ALL INFORMATION IS SUBJECT
TO CHAN
GE BASED ON ADDITION OF ANY OPTIONAL
EQUIPME
NT AND/OR ACCESSORIES. PLEASE CONSULT THE
FACTORY
FOR PROJECT SPECIFIC ESTIMATES IF
ADDITIO
NAL OPTIONS OR ACCESSORIES ARE REQUIRED.
RECOM
MEND STACK RUN IS MINIMUM 24" STRAIGHT OFF
THE RE
AR OF THE BOILER, PRIOR TO MAKING A
DIRECTI
LOCAL C
ODES CAN SUPERCEDE FULTON RECOMMENDED
CLEARA
*SIZE D
A
R
L
D
96 5/8
MAX ALLOWABLE WORKING PRESSURE:
BOILER OUTPUT:
MINIMUM INCOMING GAS PR
ESSURE:
150 PSI
2,008,500 BTU/HR
2,070 LBS/HR
116 SQ. FT.
333 GAL.
5,100 LBS.
7,864 LBS.
6,000 LBS.
EQUIPMENT SPECIFICATION CHART
APPROXIMATE FLOODED WE
MINIMUM DRAFT REQUIREM
BURNER MOTOR WITH VFD:
BURNER TURNDOWN:
9,400 LBS.
10:1
-0.25" W.C.
7.5 HP
APPROXIMATE SHIPPING WE
APPROXIMATE OPERATING
APPROXIMATE DRY WEIGHT:
WATER CAPACITY (OPERATI
NG):
NET EFFECTIVE HEATING SURFACE:
STEAM OUTPUT/MIN. SRV CAPACITY:
2,392 CU FT/HR
BOILER INPUT:
3" W.C.
BOILER INPUT: (NATURAL GAS)
2,392,000 BTU/HR
ELECTRICAL REQUIREMENTS
VOLTAGE OPERATING FLA
480/3/60
15 AMPS
NOTE: OPERATING FULL LOAD AMPERAGE (FLA)
REFERS TO THE BOILER'S RATED CURRENT DRAW
AT HIGH FIRE. SUBJECT TO CHANGE BASED ON
BOILER CONFIGURATION.
130
CLEARANCE REQUIRED
FOR BURNER REMOVAL
9
Figure 11 - 40/50/60-HP Model VSRT Dimensions -
Side View (All dimensions in inches)