EasyManua.ls Logo

Future Design FDC-8300 - Page 40

Default Icon
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Stay at least minutes in still-
air room
room temperature 25 3 C
20
AL
Stay at least minutes in still-
air room
room temperature 25 3 C
20
AL
Perform step 10 to calibrate of compensation, if
required.
The
DIP switch is set for T/C input.
offset cold junctionPerform step 10 to calibrate of compensation, if
required. The DIP switch is set for T/C input.
offset cold
junction
Setup the equipments according to the following diagram for
calibrating
the
cold junction compensation. Note that a K type
thermocouple must be used.
Setup the equipments according to the following diagram for
calibrating the cold junction compensation. Note that a K type
thermocouple must be used.
Step 10.Step 10.
Press scroll key and the display will show . Change the
ohm's value to 300 ohms .Press scroll key for at least 3 seconds.
The display will blink a moment and two values are obtained for SR1
and REF1 (last step). Otherwise, if the display didn't blink or if any
value obtained for SR1 and REF1 is equal to -199.9 or 199.9 ,
then the calibration fails.
Press scroll key and the display will show . Change the
ohm's value to 300 ohms .Press scroll key for at least 3 seconds.
The display will blink a moment and two values are obtained for SR1
and REF1 (last step). Otherwise, if the display didn't blink or if any
value obtained for SR1 and REF1 is equal to -199.9 or 199.9 ,
then the calibration fails.
Perform step 7 to calibrate function ( if required ) for input 1.mAPerform step 7 to calibrate function ( if required ) for input 1.mA
Change the DIP switch for mA input. Press scroll key until the display
shows
.Send
a 20 mA signal to terminals 19 and 20 in
correct polarity. Press scroll key for at least 3 seconds . The display
will blink a moment and a new value is obtained . Otherwise , if the
display didn't blink or if the obtained value is equal to -199.9 or 199.9,
then the calibration fails.
Change the DIP switch for mA input. Press scroll key until the display
shows .Send a 20 mA signal to terminals 19 and 20 in
correct polarity. Press scroll key for at least 3 seconds . The display
will blink a moment and a new value is obtained . Otherwise , if the
display didn't blink or if the obtained value is equal to -199.9 or 199.9,
then the calibration fails.
Perform step 8 to calibrate as well as CT function ( if required )
for
input
2.
voltagePerform step 8 to calibrate as well as CT function ( if required )
for input 2.
voltage
Press scroll key until the display shows . Send a 10 V signal to
terminals 15
and 16 in correct polarity. Press scroll key for at least 3
seconds . The display will blink a moment and a new value is obtained .
Otherwise , if the display didn't blink or if the obtained value is equal
to -199.9 or 199.9 , then the calibration fails.
Press scroll key until the display shows . Send a 10 V signal to
terminals 15 and 16 in correct polarity. Press scroll key for at least 3
seconds . The display will blink a moment and a new value is obtained .
Otherwise , if the display didn't blink or if the obtained value is equal
to -199.9 or 199.9 , then the calibration fails.
Press scroll key until the display shows . Send a 20 mA signal
to
terminal
15 and 16 in correct polarity. Press scroll key for at least
3 seconds . The display will blink a moment and a new value is obtained .
Otherwise , if the display didn't blink or if the obtained value is equal to
-199.9 or 199.9, then the calibration fails.
Press scroll key until the display shows . Send a 20 mA signal
to terminal 15 and 16 in correct polarity. Press scroll key for at least
3 seconds . The display will blink a moment and a new value is obtained .
Otherwise , if the display didn't blink or if the obtained value is equal to
-199.9 or 199.9, then the calibration fails.
Step 6.Step 6.
Step 7.Step 7.
Step 8.Step 8.
Step 9.Step 9.
*
*
Perform step 9 to calibrate function ( if required ) for input 2.mAPerform step 9 to calibrate function ( if required ) for input 2.mA
*
*
Figure 6.2
Cold Junction
Calibration Setup
Figure 6.2
Cold Junction
Calibration Setup
FDC-8300
19
20
K+
K
5520A
Calibrator
5520A
Calibrator
K-TC
The 5520A calibrator is configured as K type thermocouple output with
internal compensation. Send a 0.00 C signal to the unit under
calibration.
The 5520A calibrator is configured as K type thermocouple output with
internal compensation. Send a 0.00 C signal to the unit under
calibration.
1 2 3 4
ON
1 2 3 4
ON
DIP Switch PositionDIP Switch Position
mA inputmA input
DIP Switch PositionDIP Switch Position
TC inputTC input
UM83001A-August-2024
40