GALaxy eHydro Elevator Controller Section 7 Main CPU Adjustable Variables
7-2
Table 7-1: Car Motion
Field Variable
Min
Max
Initial
Units
Description
Shrt Fl Dn SD
0
30
0
sec
Short Floor Down Slowdown. Hydro - There are no slow
down magnets between short floors. This is a timer to
run down high speed in seconds. If the timer is set to
zero, controller will immediately level looking for the
other zone. This parameter should only be used if second
selector is utilized.
Shrt Fl Up SD
0
30
0
sec
Short Floor Up Slowdown. Hydro - There are no slow
down magnets between short floors. This is a timer to
run up high speed in seconds. If the timer is set to zero,
controller will immediately level looking for the other
zone. This parameter should only be used if second
selector is utilized.
ShrtMidF
DnSD
0
30
0
sec
Short Mid Floor Down Slowdown. Hydro - To be used in
second and higher short floor. There are no slow down
magnets between short floors. This is a timer to run
down high speed in seconds. If the timer is set to zero,
controller will immediately level looking for the other
zone. This parameter should only be used if second
selector is utilized.
ShrtMidF
UpSD
0
30
0
sec
Short Mid Floor Up Slowdown. Hydro - To be used in
second and higher short floor. There are no slow down
magnets between short floors.
This is a timer to run up high speed in seconds. If the
timer is set to zero, controller will immediately level
looking for the other zone. This parameter should only be
used if second selector is utilized.
Soft Stop Tim
0.2
5
1
sec
Soft Stop Time. The time the motor is kept running after
the valve is turned off.
StopOn
PosCnt
0
1
0
-
Stop On Position Count. Enable to stop the elevator on
position pulse count. Used only for tapeless application.
This requires cons file setting to be enabled and
readjustment of leveling sensors for it to work.