GALaxy eHydro Elevator Controller Section 7 – Main CPU Adjustable Variables
7-4
Door Delay Time. Delay time between DO and DC to
switch when opening or closing the door.
Door Fail Time. Time with power on the door without
getting the door open limit.
Electric Eye Test for Automatic Freight Doors
Electric Eye Time-out Time. If the Electric Eye or
detector edge is on continuously for this amount of
time, it will be flagged as timed-out and the controller
will ignore the EE input and close the door on
nudging. When set to zero, this feature is disabled.
Fire phase 1 Door Close Time-out. The amount of
time it will take before the car doors start to close
while the car is on Independent or Attendant service
prior to recalling the elevator on Fire Phase 1.
Fault Time. Delay time before allowing the car to run
after a fault occurs.
Freight Door Close Time-out. The amount of time
prior to closing the doors on automatic freight door
operation.
Freight Door Power Door Open Time. The amount of
time to turn on the power door open relay on
automatic freight door operation.