GALaxy eHydro Elevator Controller Section 7 Main CPU Adjustable Variables
7-17
Table 7-4: Service Options
Field Variable
Min
Max
Initial
Units
HEOF Override
0
3
0
-
Hall Elevator off Override.
1= Override Independent Service after timer expires
and then recall the car.
2 = Override Attendant Service after timer expires
and then recall the car.
IND DoorCl CC
0
1
0
-
Independent Door Close Car Call. Enable to close the
doors from a car call when the elevator is on
Independent.
Ind Over Sec
0
7
0
-
Independent Overrides Security.
1 = Allow independent service to override security car
call lockouts.
2 = Override Security Floor Mask configurations.
4 = Override remote car call station.
IND Rcl 2 Lby
0
1
0
-
Independent Recall to Lobby. Forces the car to recall
to the lobby when on independent and no calls are
made
Ins Door Clos
0
1
0
-
Inspection Door Close.
1 = The door close output will turn on when the up or
down inspection run button is pressed.
INSEC Out Ctl
0
1
0
-
INSEC - In Security Output Invert. Output located on
the car call security Board.
0 = Disabled
1 = Enabled
Lobby Floor
Bottom
Floor
Top
Floor
1
floor
Lobby Floor.
LW Anti-nuisn
0
50
0
count
Load Weighing Anti-Nuisance. Set to the maximum
number of car calls that can been entered before all
car calls are cancelled without the load switch LWA
input on. Once the load switch is on, all car calls will
stay latched. 0 = Disabled.