GALaxy eHydro Elevator Controller Section 7 Main CPU Adjustable Variables
7-22
Table 7-5: Emergency Services
Field Variable
Min
Max
Initial
Units
ALT Fire Flr
Bottom
Floor
Top
Floor
2
floor
Alternate Fire Floor.
AltRcl FS Off
0
3
0
-
Alternate Floor Recall Fire Service Off.
+1 = Have the elevator recall back to the alternate
floor when the lobby fire switch is turned to the off
position and car recalled to the main fire floor.
+2 = Allows the car to return to the alternate
landing even if sensor was reset
Aux. Fire Sw
0
1
0
-
Auxiliary Fire Switch. When set, the controller
expects an auxiliary hall fire switch to be used.
CB Buzz ctrl
0
1
0
-
Code blue Buzzer Control.
1 = Turn buzzer on while in code blue recall
CB over FS
0
1
0
-
Code Blue over Fire Service.
+1 Enable to have code blue prevent car from
recalling in FS
CB Over Ind
0
1
0
Code Blue Override Independent.
1 = Wait for timer to expire and then recall the car
CB SingleCall
0
1
0
-
Code Blue Single Car Call.
0 = Car on Code Blue operation allows multiple car
calls on Hospital Service.
1 = Allow only a single call once place on Hospital
Service.
ClDoor F1 Rcl
0
1
0
-
Close Door After Fire phase 1 Recall.
1 = Elevator will close the doors after phase 1 recall
and reopen from a hall call (Denver Fire service
amendment)
Em Pwr Floor
Bottom
Floor
Top
Floor
1
floor
Emergency Power Recall Floor.