GALaxy eHydro Elevator Controller Section 7 Main CPU Adjustable Variables
7-32
Table 7-6: Group Dispatch
Field Variable
Min
Max
Initial
UpPk Trig Tim
0
3200
60
Up Peak Trigger Time. The time interval to count the
number of up peak triggers.
Table 7-7: Group Options
Field Variable
Min
Max
Initial
Units
Description
1st Rcl EPSF2
0
Number
Cars
2
Car
First Return Car Emergency Power Service Feeder
2. This will be the first car recalled in Emergency
Power (the rest are done sequentially in a loop) for
power feeder 2
1st Run EPSF2
0
Number
Cars
2
Car
First Run Car Emergency Power Service Feeder 2.
This will be the first car selected to run on emergency
power (the rest are done sequentially in a loop) for
power feeder 2
1stEP Run Car
0
Number
Cars
1
Car
First Emergency Power Run Car. This is the first car
selected to run. If this car cannot run, the next
consecutive car is selected.
1stRecall Car
0
Number
Cars
1
Car
First Recall Car. This is the first car allowed to recall
during the emergency power recall sequence. The
recall sequence continues in consecutive order and
then loops around until all cars are recalled.
2nd IR Car
0
Number
Cars
0
Car
2nd Inconspicuous Riser Car. Set this option to have
a second car answer the Inconspicuous Risers.
2nd Riser Ctl
0
Number
Cars
0
Car
Second Riser Control. Defines the second riser
operation.
0 = Car defined for second riser answer second riser
call and standard hall calls.
1 = Car defined for second riser answer only second
riser calls.
2 = Second riser call or’ed with standard riser calls if
second riser operation not selected from input.