GALaxy eHydro Elevator Controller Section 7 Main CPU Adjustable Variables
7-53
Table 7-9: System Options
Field Variable
Min
Max
Initial
CAN Sync Cnt
0
7
4
CAN Sync Count. Frequency to update CAN Bus
devices. Units are 1/4 seconds. It sets Synchronization
Count in 250 millisecond increments
COM1 Baud
0
9
6
Com 1 User Interface Baud Rate. Selects the bit rate
of the COM 1 serial port.
0 = 2400 bps,
1 = 4800 bps,
2 = 9600 bps,
3 = 19200 bps,
4 = 38400 bps,
5 = 57600 bps,
6 = 115200 bps,
7 = 219254 bps,
8 = 226562.5 bps,
9 = 234375 bps.
COM1 Port Sel
0
7
6
Com 1 Port Select. Selects the operation of COM 1
port.
0 = Comm Diag,
1 = Comm Debug,
2 = Galcom,
3 = DL20,
4 = Galcom Wireless,
5 = Galcom Ethernet,
6 = Galcom Wireless Flow Control,
7 = Galcom Ethernet Flow Control
COM2 Baud
0
9
3
Com 2 User Interface Baud Rate. Selects the bit rate
of the COM 2 serial port.
0 = 2400 bps,
1 = 4800 bps,
2 = 9600 bps,
3 = 19200 bps,
4 = 38400 bps,
5 = 57600 bps,
6 = 115200 bps,
7 = 219254 bps,
8 = 226562.5 bps,
9 = 234375 bps.