6.0 MODULE SETTINGS
6.1 MAIN FIRE ALARM MODULE
Class A / B Selection: JW1 & JW2 are connected from 1 to 2 for Initiating Circuit Class B (Style B) operation, and from 2 to 3 for Class
A (Style D) operation.
Note that the Class A/B selection affects all Initiating Circuits, and must be used with the correct Configuration DIP Switch Setting.
Circuit Expander On an Flex 4 only, remove the jumper on JW4 if a CEM Circuit Expander Module is field installed. The module
Module: is plugged into P6 & P7.
Relay Module: Remove jumper JW3 if a RY4 or RY8 Relay Module is installed. The Relay Module is plugged into P1.
Digital Communicator: Remove jumper JW6 if a DACT Digital Communicator is installed. The Digital Communicator is plugged into P8.
City Tie: Remove jumper JW6 if a PRM Polarity Reversal/City Tie module is installed. The module is plugged into P8.
Battery: Connected to P2 (+’ve) & P3 (-’ve) via the factory installed cables.
Transformer: Factory wired to P4 & P5, do not disconnect.
JW5 There should be no jumper here; do not use.
SW9, SW11, SW13 Configuration DIP Switches.
Battery Fuse F1: Replace with 10 Amp, 1-1/4" Fast Acting Fuse