EasyManua.ls Logo

Gamewell Flex 4 - Module System Configuration

Default Icon
35 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 29 of 35
10.0 MODULE SYSTEM CONFIGURATION
Configuration of the Flex 4 and Flex 8 Control Panels is easily accomplished by DIP Switch and Jumper Settings.
For DIP Switches, 0 = switch “off”, 1 = Switch “on’).
On the Main Fire Alarm Board ...
Function DIP Switch Switch “Off” Switch “On”
Indicating Circuit #1
Audible Device (Bell) Only
Switch 13, #1 Silenceable Non-Silenceable
Indicating Circuit #2
Audible or Visual Device
Switch 13, #2 Silenceable Non-Silenceable
Switch 13, #3 Audible Device (Bell/Horn) Visual Device (Strobe)
# Remote Annunciators
Switch 13, #4
5 off, 4 off = None 5 off, 4 on = One
5 on, 4 off = Two 5 on, 4 on = Three
Switch 13, #5
Manual Signal Silence Switch 13, #6 Disabled Enabled
Fire Drill Switch 13, #7 Disabled Enabled
Auxiliary Disconnect Switch 13, #8 Disabled Enabled
Initiating Circuit #1
Alarm Only
Switch 11, #1 Normal Alarm Verified Alarm
Initiating Circuit #2
Alarm Only
Switch 11, #2 Normal Alarm Verified Alarm
Initiating Circuit #3
Alarm or Waterflow
Switch 11, #3 Normal Verified Alarm / Retarded Waterflow
Switch 11, #4 Alarm Waterflow
Initiating Circuit #4
Alarm or Supervisory
Switch 11, #5 Normal Verified Alarm (no effect on Supv.)
Switch 11, #6 Alarm Supervisory
Switch 11, #7
Non-Latching Supervisory
(No effect on Alarm)
Latching Supervisory
(No effect on Alarm)
Not Used Switch 11, #8 ----------------- -----------------
Signal Code
Switch 9, #1
2 off, 1 off = Temporal Code 2 off, 1 on = Continuous
2 on, 1 off = March Time 2 on, 1 on = California Code
Switch 9, #2
Auto Signal Silence
Switch 9, #3
4 off, 3 off = Disabled 4 off, 3 on = 5 Minutes
4 on, 3 off = 10 Minutes 4 on, 3 on = 20 Minutes
Switch 9, #4
Signal Silence Inhibit Switch 9, #5 None 1 Minute
Initiating Circuit Style / Class Switch 9, #6 Class B (Style B) Class A (Style D)
Auxiliary Devices Switch 9, #7 Non-Silenceable Silenceable
AC Power Fail Delay to
Aux. Devices
Switch 9, #8
24 Hour Standby
Standard
60 Hour Standby
Standard
Notes:
& AFTER ANY CONFIGURATION SWITCHES ARE CHANGED, IT IS NECESSARY TO PERFORM A SYSTEM RESET !!
& Only Indicating Circuit 2 may be configured for Visual Devices.
& If Initiating Circuit 3 is configured as Waterflow, the corresponding Verified selection becomes a Retard
selection.
Note: Do not use Retard Operation with any external Retarding device; maximum Retard may not exceed 120
seconds.
& If Initiating Circuit 4 is configured as Alarm, the corresponding Latching selection has no effect.
& If Initiating Circuit 4 is configured as Supervisory, the corresponding Verified selection has no effect.
& The selection of Class A/B (Style Z/Y) Indicating Circuits is only a matter of how they are wired. No Programming
is necessary See Connection Information (Figures 9 & 10).
& If Class A (Style D) Initiating Circuits are selected, the appropriate Board Jumpers must also be set.
Class B Initiating Circuits 1 & 2 combine to create Class A Circuit #1, and Class B Initiating Circuits 3 & 4
combine to create Class A Circuit #2.
In Class A operation, the DIP Switches for Circuits 3 & 4 are ignored except for an Flex 4 with a CEM Circuit
Expander Module. LED Indicators for Circuits 3 & 4 are non-functional except for an Flex 4 with a CEM Circuit
Expander Module.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com

Table of Contents

Related product manuals