3.1 MODELS
Model: Flex 4 Fire Alarm Control Panel with four Class B (Style B) or two Class A (Style D) Initiating Circuits,
and two Power Limited Class A/B (Style Z/Y) Indicating Circuits (maximum 1.70 amperes each,
5 amperes total) with individual trouble indicators. Common Alarm & Trouble Relays. Interface
for Remote Trouble Indicator RTI and/or 1 to 3 of RA8 Remote Multiplex Annunciators.
Resettable Power Supply for Four Wire Smoke or Heat Detectors . May have one DACT or
PRM, and one CEM installed. May also have one of RY4 or RY8 installed.
Model: Flex 8 Fire Alarm Control Panel with eight Class B (Style B) or four Class A (Style D) Initiating Circuits,
and four Power Limited Class A/B (Style Z/Y) Indicating Circuits (maximum 1.70 amperes each,
5 amperes total) with individual trouble indicators. Common Alarm & Trouble Relays. Interface
for Remote Trouble Indicator RTI and/or 1 to 3 of RA8 Remote Multiplex Annunciators.
Resettable Power Supply for Four Wire Smoke or Heat Detectors May have one DACT or
PRM, and one CEM installed. May also have one of RY4 or RY8 installed.
Model: CEM Circuit Expander Module for the Flex 4 to increase the system capacity to that of the Flex 8.
Model: RY4 Relay Module for Flex 4 or Flex 8. Adds four configurable Relays Form C rated 1A, 28 VDC.
Model: RY8 Relay Module for Flex 4 or Flex 8. Adds eight configurable Relays Form C rated 1A, 28 VDC.
Model: DACT Dual Line Digital Alarm Communicator Transmitter Module.
Model: PRM City Tie / Reverse Polarity Module.
3.2 ACCESSORIES
Model: RA8 8 Zone Remote Annunciator (UL Listed)
Model: RTI Remote Trouble Indicator (UL Listed)
Model: 30177 End of Line Resistor (UL Listed)
Model: CFG DACT programming tool
3.3 BATTERIES
Model: B12V4 12 Volt 4 Ampere-Hour (2 required)
Model: B12V7 12 Volt 7 Ampere-Hour (2 required)
Model: B12V12 12 Volt 10 Ampere-Hour (2 required)