38  1200C-2000C Fire Alarm Control Panel, Repeater, and Black Box Installation Manual 
Appendix C: Maximum zones and loops 
The maximum number of zones and zone modules, loops and loop modules for each 
panel are shown in the table below. 
Table 13: 1200C-2000C maximum zones and loops 
Control 
panel 
Maximum number 
of zones 
Maximum number 
of zone modules 
Maximum number 
of loops 
Maximum number 
of loop modules 
FP1216C  16  1 x ZE2016  4A / 8B  2 x LC1502 
FP1264C  64   1 x ZE2064  4A / 8B  2 x LC1502 
FR1216C  16   1 x ZE2016  N/A  N/A 
FR1264C  64  1 x ZE2064  N/A  N/A 
FP2864C  64   4 x ZE2016  8A / 8B  4 x LC1502 
FP28255C  255  4 x ZE2064  8A / 8B  4 x LC1502 
FR2064C  64   4 x ZE2016  N/A  N/A 
FR20255C  255   4 x ZE2064  N/A  N/A 
FRG20255C  255  4 x ZE2064  N/A  N/A 
GR2064C  64   4 x ZE2016  N/A  N/A 
 
Note: For control purposes the absolute maximum number of zones is 255.