EasyManua.ls Logo

GE 469

GE 469
307 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-76 469 Motor Management Relay GE Power Management
4.12 S11 MONITORING 4 SETPOINT PROGRAMMING
4
4.12.4 PULSE OUTPUT
This feature configures one or more of the output relays as a pulsed output. When the programmed interval
has transpired the assigned relay will be activated for 1 second.
This feature should be programmed such that no more than one pulse per second will be required or
the pulsing will lag behind the interval activation.
y
PULSE OUTPUT
y
[ENTER] for more
POS kWh PULSE OUTPUT
RELAY: Off
Range: Off, Latched, Unlatched
POS kWh PULSE OUTPUT
INTERVAL: 1 kWh
Range: Breaker, Contactor
POS kvarh PULSE OUT
RELAY: Off
Range: Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3,
Alarm & Auxiliary3, Auxiliary2, Aux2 & Aux3, Auxiliary3
POS kvarh PULSE OUT
INTERVAL: 1 kvarh
Range: 10 to 1000 ms, step 10
NEG kvarh PULSE OUT
RELAY: Off
Range: Disabled, 52 Closed, 52 Open/Closed
Message seen only if Starter Type is Breaker
NEG kvarh PULSE OUT
INTERVAL: 1 kvarh
Range: On, Off
RUNNING TIME PULSE
RELAY: Off
Range: Disabled, 52 Closed, 52 Open/Closed
Message seen only if Starter Type is Breaker
RUNNING TIME PULSE
INTERVAL: 0 sec
Range: On, Off
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
NOTE

Table of Contents

Other manuals for GE 469

Related product manuals