6-20 469 Motor Management Relay GE Power Management
6.4 MEMORY MAP 6 COMMUNICATIONS
6
LAST TRIP
DATA ALARM
continued
0243 Pre-Trip Real Power 50000 50000 1 kW F12 0
0245 Pre-Trip Reactive Power –50000 50000 1 kvar F12 0
0247 Pre-Trip Apparent Power 0 50000 1 kVA F1 0
0248 Pre-Trip Power Factor –99 100 1 - F21 0
0249 Analog Input #1 Pre-Trip 50000 50000 1 - F12 0
024B Analog Input #2 Pre-Trip 50000 50000 1 - F12 0
024D Analog Input #3 Pre-Trip –50000 50000 1 - F12 0
024F Analog Input #4 Pre-Trip –50000 50000 1 - F12 0
0251 Reserved
...
025B Reserved
025C Pre-Trip Temp. of Hottest Stator RTD (
o
F) 58 482 1 °F F4 32
025D Pre-Trip Temp. of Hottest Bearing RTD (
o
F) –58 482 1 °F F4 32
025E Pre-Trip Temp. of Hottest Other RTD (
o
F) –58 482 1 °F F4 32
025F Pre-Trip Temp. of Hottest Ambient RTD (
o
F) –58 482 1 °F F4 32
0260 Reserved
... ...
0264 Reserved
0265 Remote Alarm Status 0 4 1 - FC123 0
STATUS 0266 Pressure Switch Alarm Status 0 4 1 - FC123 0
0267 Vibration Switch Alarm Status 0 4 1 - FC123 0
0268 Digital Counter Alarm Status 0 4 1 - FC123 0
0269 Tachometer Alarm Status 0 4 1 - FC123 0
026A General Switch A Alarm Status 0 4 1 - FC123 0
026B General Switch B Alarm Status 0 4 1 - FC123 0
026C General Switch C Alarm Status 0 4 1 - FC123 0
026D General Switch D Alarm Status 0 4 1 - FC123 0
026E Thermal Capacity Alarm 0 4 1 - FC123 0
026F Overload Alarm Status 0 4 1 - FC123 0
0270 Undercurrent Alarm Status 0 4 1 - FC123 0
0271 Current Unbalance Alarm Status 0 4 1 - FC123 0
0272 Ground Fault Alarm Status 0 4 1 - FC123 0
0273 RTD #1 Alarm Status 0 4 1 - FC123 0
0274 RTD #2 Alarm Status 0 4 1 - FC123 0
0275 RTD #3 Alarm Status 0 4 1 - FC123 0
0276 RTD #4 Alarm Status 0 4 1 - FC123 0
0277 RTD #5 Alarm Status 0 4 1 - FC123 0
0278 RTD #6 Alarm Status 0 4 1 - FC123 0
0279 RTD #7 Alarm Status 0 4 1 - FC123 0
027A RTD #8 Alarm Status 0 4 1 - FC123 0
027B RTD #9 Alarm Status 0 4 1 - FC123 0
027C RTD #10 Alarm Status 0 4 1 - FC123 0
027D RTD #11 Alarm Status 0 4 1 - FC123 0
Table 6–1: 469 MEMORY MAP (Sheet 3 of 43)