6-52 469 Motor Management Relay GE Power Management
6.4 MEMORY MAP 6 COMMUNICATIONS
6
ANALOG
OUTPUTS
continued
1BEC RTD #10 Minimum (in Fahrenheit) –58 482 1 °F F4 –57
1BED RTD #10 Maximum (in Fahrenheit) –58 482 1 °F F4 482
1BEE RTD #11 Minimum (in Fahrenheit) –58 482 1 °F F4 –57
1BEF RTD #11 Maximum (in Fahrenheit) –58 482 1 °F F4 482
1BF0 RTD #12 Minimum (in Fahrenheit) –58 482 1 °F F4 –57
1BF1 RTD #12 Maximum (in Fahrenheit) –58 482 1 °F F4 482
1BF2 Reserved
... ...
1BF7 Reserved
1BF8 Analog Input Diff 1-2 Minimum –50000 50000 1 - F12 0
1BFA Analog Input Diff 1-2 Maximum –50000 50000 1 - F12 100
1BFC Analog Input Diff 3-4 Minimum –50000 50000 1 - F12 0
1BFE Analog Input Diff 3-4 Maximum –50000 50000 1 - F12 100
1C00 Reserved
...
1C0A Reserved
ANALOG
INPUT 1
1C0B Analog Input 1 Setup 0 3 1 - FC129 0
1C0C Reserved
...
1C0F Reserved
1C10 1st and 2nd char. of Analog Input 1 Units 0 65535 1 - F22 ‘Un’
...
1C12 5th and 6th char. of Analog Input 1 Units 0 65535 1 - F22 ‘ ‘
1C13 Analog Input 1 Minimum –50000 50000 1 - F12 0
1C15 Analog Input 1 Maximum –50000 50000 1 - F12 100
1C17 Block Analog Input 1 From Start 0 5000 1 s F1 0
1C18 Analog Input 1 Alarm 0 2 1 - FC115 0
1C19 Analog Input 1 Alarm Relays 0 6 1 - FC113 0
1C1A Analog Input 1 Alarm Level –50000 50000 1 - F12 10
1C1C Analog Input 1 Alarm Pickup 0 1 1 - FC130 0
1C1D Analog Input 1 Alarm Delay 1 3000 1 s F2 1
1C1E Analog Input 1 Alarm Events 0 1 1 - FC103 0
1C1F Analog Input 1 Trip 0 2 1 - FC115 0
1C20 Analog Input 1 Trip Relays 0 3 1 - FC111 0
1C21 Analog Input 1 Trip Level –50000 50000 1 - F12 20
1C23 Analog Input 1 Trip Pickup 0 1 1 - FC130 0
1C24 Analog Input 1 Trip Delay 1 3000 1 s F2 1
1C25 1st and 2nd char. of Analog Input 1 Name 0 65535 1 - F22 ‘An’
...
1C2A 11th and 12th char. of Analog Input 1 Name 0 65535 1 - F22 ‘ ‘
1C2B Reserved
...
1C4A Reserved
Table 6–1: 469 MEMORY MAP (Sheet 35 of 43)
GROUP ADDR
(HEX)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
DEFAULT