GE Power Management 469 Motor Management Relay 6-57
6 COMMUNICATIONS 6.4 MEMORY MAP
6
SPEED2
O/L SETUP
continued
1E36 Speed2 Time to Trip at 10.0
×
FLA 5 999999 1 s F10 56
1E38 Speed2 Time to Trip at 15.0
×
FLA 5 999999 1 s F10 56
1E3A Speed2 Time to Trip at 20.0
×
FLA 5 999999 1 s F10 56
1E3C Reserved
...
1E4F Reserved
1E50 Speed2 Minimum Allowable Line Voltage 70 95 1 %Rated F1 80
1E51 Speed2 Stall Current at Min Vline 200 1500 1
×
FLA F3 480
1E52 Speed2 Safe Stall Time at Min Vline 5 9999 1 s F2 200
1E53 Speed2 Accel. Intersect at Min Vline 200 1500 1
×
FLA F3 380
1E54 Speed2 Stall Current at 100% Vline 200 1500 1
×
FLA F3 600
1E55 Speed2 Safe Stall Time at 100% Vline 5 9999 1 s F2 100
1E56 Speed2 Accel. Intersect at 100% Vline 200 1500 1
×
FLA F3 500
1E57 Reserved
...
1E8F Reserved
SPEED2
UNDER
CURRENT
1E90 Block Speed2 Undercurrent from Start 0 15000 1 s F1 0
1E91 Speed2 Undercurrent Alarm 0 2 1 - FC115 0
1E92 Reserved
1E93 Speed2 Undercurrent Alarm Pickup 10 95 1
×
FLA F3 70
1E94 Speed2 Undercurrent Alarm Delay 1 60 1 s F1 1
1E95 Speed2 Undercurrent Alarm Events 0 1 1 - FC103 0
1E96 Speed2 Undercurrent Trip 0 2 1 - FC115 0
1E97 Reserved
1E98 Speed2 Undercurrent Trip Pickup 10 99 1
×
FLA F3 70
1E99 Speed2 Undercurrent Trip Delay 1 60 1 s F1 1
1E9A Reserved
...
1EAF Reserved
SPEED2
ACCELERA-
TION
1EB0 Speed2 Acceleration Timer From Start 10 2500 1 s F2 100
1EB1 Acceleration Timer From Speed One to Two 10 2500 1 s F2 100
1EB2 Speed Switch Trip Speed2 Delay 10 2500 1 s F2 50
1EB3 Speed2 Rated Speed 100 7200 1 RPM F1 3600
1EB4 Reserved
...
1EFF Reserved
ANALOG
INPUT 1-2
DIFF.
1F00 Analog In Differential 1-2 Enable 0 1 1 - FC126 0
1F01 1
st
and 2
nd
char of Analog In Diff 1-2 Name 0 65535 1 - F22 An’
...
1F06 11
th
and 12
th
char of Analog In Diff 1-2 Name 0 65535 1 - F22
1F07 Analog In Differential 1-2 Comparison 0 1 1 - FC145 0
1F08 Analog In Differential 1-2 Logic 0 2 1 - FC146 0
1F09 Analog In Differential 1-2 Active When 0 1 1 - FC147 0
Table 6–1: 469 MEMORY MAP (Sheet 40 of 43)
GROUP ADDR
(HEX)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
DEFAULT

Table of Contents

Other manuals for GE 469