GE Power Management 469 Motor Management Relay 6-59
6 COMMUNICATIONS 6.4 MEMORY MAP
6
Event Recorder / Trace Memory (Addresses 3000 -3FFF)
EVENT
RECORDER
3000 Event Recorder Last Reset (2 words) N/A N/A N/A N/A F18 N/A
3002 Total Number of Events Since Last Clear 0 65535 1 N/A F1 0
3003 Event Record Selector (1=newest, 40=oldest) 1 40 1 N/A F1 1
3004 Cause of Event 0 131 1 - FC134 0
3005 Time of Event (2 words) N/A N/A N/A N/A F19 N/A
3007 Date of Event (2 words) N/A N/A N/A N/A F18 N/A
3009 Motor Speed During Event 0 1 1 - FC135 0
300A Event Tachometer RPM 0 3600 1 RPM F1 0
300B Event Phase A Current 0 100000 1 A F9 0
300D Event Phase B Current 0 100000 1 A F9 0
300F Event Phase C Current 0 100000 1 A F9 0
3011 Event Motor Load 0 2000 1 FLA F3 0
3012 Event Current Unbalance 0 100 1 % F1 0
3013 Event Ground Current 0 500000 1 A F11 0
3015 Event Phase A Differential Current 0 5000 1 A F1 0
3016 Event Phase B Differential Current 0 5000 1 A F1 0
3017 Event Phase C Differential Current 0 5000 1 A F1 0
3018 Event Hottest Stator RTD 0 12 1 - F1 0
3019 Event Temperature of Hottest Stator RTD –50 250 1 °C F4 0
301A Event Hottest Bearing RTD 0 12 1 - F1 0
301B Event Temperature of Hottest Bearing RTD –50 250 1 °C F4 0
301C Event Hottest Other RTD 0 12 1 - F1 0
301D Event Temperature of Hottest Other RTD –50 250 1 °C F4 0
301E Event Hottest Ambient RTD 0 12 1 - F1 0
301F Event Ambient RTD Temperature –50 250 1 °C F4 0
3020 Event Voltage Vab 0 20000 1 V F1 0
3021 Event Voltage Vbc 0 20000 1 V F1 0
3022 Event Voltage Vca 0 20000 1 V F1 0
3023 Event Voltage Van 0 20000 1 V F1 0
3024 Event Voltage Vbn 0 20000 1 V F1 0
3025 Event Voltage Vcn 0 20000 1 V F1 0
3026 Event System Frequency 0 12000 1 Hz F3 0
3027 Event Real Power –50000 50000 1 kW F12 0
3029 Event Reactive Power –50000 50000 1 kvar F12 0
302B Event Apparent Power 0 50000 1 kVA F1 0
302C Event Power Factor –99 100 1 - F21 0
302D Event Analog Input #1 –50000 50000 1 - F12 0
302F Event Analog Input #2 –50000 50000 1 - F12 0
3031 Event Analog Input #3 –50000 50000 1 - F12 0
3033 Event Analog Input #4 –50000 50000 1 - F12 0
3035 Event Torque 0 9999999 1 Nm/ftlb F2 0
3037 Reserved
Table 6–1: 469 MEMORY MAP (Sheet 42 of 43)
GROUP ADDR
(HEX)
DESCRIPTION MIN. MAX. STEP
VALUE
UNITS FORMAT
CODE
DEFAULT