EasyManua.ls Logo

GE 469

GE 469
307 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B-2 469 Motor Management Relay GE Power Management
B.1 TWO-PHASE CT CONFIGURATION APPENDIX B
B
To illustrate the point further, the diagram below shows how the current in phases A and C sum up to create
phase 'B'.
Once again, if the polarity of one of the phases is out by 180°, the magnitude of the resulting vector on a bal-
anced system will be out by a factor of 1.73.
On a three wire supply, this configuration will always work and unbalance will be detected properly. In the event
of a single phase, there will always be a large unbalance present at the interposing CTs of the relay. If for
example phase A was lost, phase A would read zero while phases B and C would both read the magnitude of
phase C. If on the other hand, phase B was lost, at the supply, phase A would be 180° out-of-phase with phase
C and the vector addition would equal zero at phase B.

Table of Contents

Other manuals for GE 469

Related product manuals