EasyManua.ls Logo

GE 469

GE 469
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1–24 469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
Motor Operating Curves
Motor operating curves as shown below:
FIGURE 1–7: Motor Operating Curves for Application Example
Control System Requirements
– All protection elements trip the breaker
– Breaker position monitoring via 52b contact only
– Only current metering is required
– Serial communication remote start from RTU
– Alarm after 100 s delay from station monitor. This is normally used to signal the
remote center when someone has gained access to the substation.
Contact Outputs
– Trip and close to breaker control circuit (Trip and Auxiliary2 relays)
– Relay failure alarm to RTU (self-test warning relay, no programming required)
– Alarm contact (setup in General Sw. A for “Station Monitor”)
– No data communications to other equipment.

Table of Contents

Other manuals for GE 469

Related product manuals