EasyManua.ls Logo

GE 469

GE 469
336 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7–8 469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 7: TESTING
A1 STATUS ZV DIGITAL INPUTS
7.2.7 Analog Inputs and Outputs
The 469 specification for analog input and analog output accuracy is ±1% of full scale.
Perform the steps below to verify accuracy. Verify the Analog Input +24 V DC with a
voltmeter.
4 to 20 mA Analog Input
Z Alter the following settings:
S12 ANALOG I/O ZV ANALOG INPUT1 Z ANALOG INPUT1: “4-20 mA
S12 ANALOG I/O ZV ANALOG INPUT1 ZV ANALOG INPUT1 MINIMUM: “0”
S12 ANALOG I/O ZV ANALOG INPUT1 ZV ANALOG INPUT1 MAXIMUM: “1000” (repeat this
value for Analog Inputs 2 to 4)
Analog output values should be ±0.2 mA on the ammeter. Measured analog input
values should be ±10 units.
Z Force the analog outputs using the following settings:
S13 TESTING ZV TEST ANALOG OUTPUT Z FORCE ANALOG OUTPUTS FUNCTION:
“Enabled”
S13 TESTING ZV TEST ANALOG OUTPUT ZV ANALOG OUTPUT 1 FORCED VALUE: “0%”
(enter desired value in percent; repeat for Analog Outputs 2 through 4)
Z Verify the ammeter readings as well as the measured analog input
readings.
For the purposes of testing, the analog input is fed in from the analog
output (see FIGURE 7–1: Secondary Injection Test Setup on page 7–2).
Z View the measured values in:
INPUT EXPECTED
STATUS (SWITCH
OPEN)
PASS /
FAIL
EXPECTED
STATUS (SWITCH
CLOSED)
PASS /
FAIL
ACCESS Open Shorted
TEST Open Shorted
STARTER STATUS Open Shorted
EMERGENCY RESTART Open Shorted
REMOTE RESET Open Shorted
ASSIGNABLE INPUT 1 Open Shorted
ASSIGNABLE INPUT 2 Open Shorted
ASSIGNABLE INPUT 3 Open Shorted
ASSIGNABLE INPUT 4 Open Shorted
TRIP COIL SUPERVISION No Coil Coil

Table of Contents

Other manuals for GE 469

Related product manuals