EL
ECTR
IC
AL  TRIPPING 
-
The 
breaker 
may 
be 
tripped 
electrically 
by any 
of  tha 
electrical 
tripping  devices 
described 
in 
these 
instructions.
.  The 
breaker 
may  also 
be 
tripped 
by  the  automatic 
overcurrent 
or 
reverse 
current 
tripping  devices,  if 
so 
equipped.  All 
these 
devices 
trip 
the 
breaker 
inasimilarmanner, 
i.e. 
·the  device 
trip 
arm 
moves 
against 
the 
trip 
paddles 
fastened  on the 
trip 
shaft
,  thus  rotating 
the 
trip 
shaft 
and displacing the 
trip 
latch. 
The 
most 
commonly 
used 
tripping device 
is 
the 
shunt 
trip 
device  connected  in the control 
circuit 
as 
shown 
in 
Fig. 
1. 
When a tripping 
signal 
is 
given, 
the shunt 
trip 
coil 
is 
energized through a nortrlally-
open  auxiliary  switch  "
a" 
-contact,  thus  tripping 
· tbe 
breaker. 
.  . 
MAINTENANCE 
BEFORE INSPECTION OR 
ANY 
MAINTENANCE 
WORK 
IS 
DONE 
BE 
SURE THAT THE BREAKER 
IS 
IN  THE  OPEN  POSITION.  ALL ELECTRICAL 
POWER,  BOTH  PRIMARY 
AND
·  CONTROL 
SOURCES,  SHOULD 
ALSO 
BE  DISCONNECTED. 
Warning:  On 
breakers 
employing 
stored-en-
ergy 
closing  mechanisms, 
care 
must 
be 
taken 
when  the 
circuit 
breaker 
is 
being 
installed 
and  when  any  inspection 
or 
maintenance work 
is 
being  done 
so 
that 
the 
breaker 
is 
in 
the 
open· 
position 
and  the  closing 
springs 
are 
· being  re15trained  by 
the 
safety pin.  The 
proce-
dure 
for 
inserting 
the safety pin 
is 
given below. 
- INSERTING 
SAFE
TY 
PIN 
-
AK
-5
0,  -
75 
and 
-100 
· 
.  (Fig 
•. 
3) 
.  . 
The  closing 
sprini 
~hould  be  charged with the 
maintenance handle 
(1) 
so 
that 
the safety pin 
(3)
-
can  be 
placed 
in 
the  hole  of  the  push 
rod 
(2). 
Continue  to op 
er
.
ate 
the maintenance· handle, 
clos-
ing  the 
breaker. 
This 
is 
done 
so 
that 
the safety 
pin 
takes 
the SJ?ring 
force
. 
- To  il)stall the 
safety 
pin of the manµal 
stored
-
energy  mechanism 
refer 
to  the 
section 
entitled 
STORED- ENERGY MANUAL  MECHANISM on page 
17 
of 
these 
instrucUons. 
With  the  safety  pin 
restraining 
the  closing 
spring 
force,  the. contacts will 
close 
s.lowly when  · 
the 
breaker 
is 
manually 
operated 
a1lowing  the 
operation 
of  the mechanism and the contact align-
ment 
~o 
be 
visually observed. 
.  .  -
. 
!allowing 
the  inspection 
period, 
the  closing 
sprmgs 
must be recharged, the 
safety 
pin 
removed 
from 
the 
push 
rod, and the pin placed 
in 
the 
retain-
ing 
spring 
clip adjacent to the push 
rod. 
Low Voltage 
Power 
Circ~it 
Breakers 
GEK-7303 
Fig. 3  {8039670)  View showing operation of 
·  AK-2-50 ·
breaker 
with manual maintenance 
handle and installation. of safety pin, 
1..  Manual maintenance 'Handle 
2. 
Push 
Rod 
3. 
Safety 
Pin 
INSPECTI
ON 
Periodic 
inspection  of  the 
circuit 
break~r 
is 
recommended ·
at 
least 
once  a 
year.
· More 
fre-
quent  inspections 
are 
recommended 
if 
severe 
load.  conditions,  dust,  moisture 
or
_ 
other 
unfavor 
able  conditions 
exist. 
A  complete  inspection 
.of the 
breaker, 
including contacts and 
arc 
quenchers, 
should  always 
be 
made 
after 
the 
breaker 
has in-
terrupted 
a 
short-circuit. 
At 
regular 
inspection periods the 
breaker 
should  -
be 
operated 
manually;  (stored energy mechanisms · 
with  the 
safety 
pin 
restraining the closing spring 
force) 
fo 
observe 
the  contact  alignment  and  to 
make 
sure 
all 
mechanism 
parts 
move  freely 
without binding 
or 
excessive friction. 
If 
the 
breaker 
remains 
-open 
or 
closed 
for 
a· 
period 
of 
six 
months 
or 
more, 
it 
is 
recommended 
that 
arrangements 
. 
be 
made  to  open  and  close 
it 
several 
times 
in  succession, . preferably  under. 
load. 
If  overheating,  not caused  by overcurrent, 
is 
observed,  a  complete  inspection 
of 
the 
breaker 
should 
be 
made including connections and contacts. 
5