117 • Appendix C - DeviceNet™ to Modbus™ Gateway
C.9.3. Common Services
Implemented for
Service
Code
Class Level Instance Level
Service Name
0E
HEX
Yes Yes Get Attribute Single
10
HEX
No Yes Set Attribute Single
32
HEX
No Yes Clear Counters
C.10. Input Object (70
HEX –
1 Instance)
C.10.1. Class Attributes (Instance 0)
Attribute
ID
Name DeviceNet
Data Type
Data Value
Access
Rule
1 Revision UINT 1 Get
C.10.2. Instance Attributes (Instance 1)
Attribute
ID
Name Description Access
Rule
Modbus
Address
1 Logic Status Logic Status of ASTAT-XT: Get 40257
2 Motor Current Current, % Im Get 40258
3 Line Voltage Line Voltage (Volts) Get 40259
4 Phase Sequence 1 – Correct Phase Seq.
0 – Wrong Phase Seq.
Get 40260
5 Hardwired inputs Get 40261
6 DIP switch Get 40262
7 Thermal Capacity Get 40293
8 Reserved Get 40264
9 Reserved Get 40265
10 Frequency Main frequency, Hz Get 40266
11 Thermistor_
Resistance
Thermistor resistance, tenth
Kohm.
Get 40267
12 Reserved Get 40268
13 Reserved Get 40269
14 Reserved Get 40270
15 Reserved Get 40271
16 Reserved Get 40272
17 Logic status at
power fail
Logic status at control power
supply turns OFF.
Get 40273
18 Elapsed Run Time Total Hours of motor runs. Get 40274
19 Number of Starts Total number of starts Get 40275
20 Last start period Duration of last start, Seconds Get 40276
21 Last start peak I Peak current during last
starting process
Get 40277
22 Time_to_Start After too many starts trip,
Seconds
Get 40278
23 Total trips Total number of trips Get 40279
24 Last Fault number # of the fault that caused trip.
# Fault
01: Over Temperature
02: Short Circuit Current
03: Overload
04: Under Current
05: Under Voltage
06: Over Voltage
07: Phase Loss
08: Phase Sequence
Get 40280