GE Grid Solutions
D25
User's Manual
GE Information 994-0081-3.00-21
47
Control Outputs, Continued
D25KE DB-25
Trip/Close
Configuration
Through the use of “Master” relays, the 32 digital outputs can be configured
as four groups of eight Trip/Close pairs, that is, 64 output connections.
Note: The Control Voltage can be up to 75 Vdc or 50 Vac. See page 152
for specifications of control outputs.
P1 connections
for Trip/Close
Use jumper wires on the Control Function Terminal block P1 to configure:
Group 1:
connect between MT (P1-6) and JMP1 (P1-3)
Group 2:
connect between MT (P1-6) and JMP2 (P1-4)
Group 3:
connect between MT (P1-6) and JMP3 (P1-7)
Group 4:
connect between MT (P1-6) and JMP4 (P1-8)
T/C 1 - 8
T/C 25 - 32
P1
T/C 9 - 16
1 2 3 4 5 6 7 8
Control
Voltage
Control
Voltage
Return
T/C 17 - 24