GE Grid Solutions
D25
User's Manual
GE Information 994-0081-3.00-21
57
Control Outputs, Continued
D25KE FACE-
40 Trip/Close
Configuration
Through the use of “Master” relays, the 32 digital outputs can be configured
as four groups of eight Trip/Close pairs: 64 output connections.
Note: The control voltage can be up to 120 Vdc. See page 152 for
specifications of control outputs.
G1 and G2
Connections for
Trip/Close
Use jumper wires on the FACE-40 terminal block G1 to configure groups 1
and 2.
Group 1:
connect between MTA (G1-39) and JMP1 (G1-37)
Group 2:
connect between MTA (G1-40) and JMP2 (G1-38)
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
G1
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
G2
Use jumper wires on the FACE-40 terminal block G2 to configure groups 3
and 4.
Group 3:
connect between MTB (G2-5) and JMP3 (G2-3)
Group 4:
connect between MTB (G2-6) and JMP4 (G2-4)